消防施工大致分为:消防水灭火系统、火灾自动报警系统、防排烟系统、应急疏散系统、气体灭火系统、泡沫灭火系统、防火分隔。
Fire fighting construction is roughly divided into: fire water extinguishing system, automatic fire alarm system, smoke control system, emergency evacuation system, gas extinguishing system, foam extinguishing system, and fire separation.
其中水灭火系统包括:室内消火栓系统、室外消火栓系统、喷淋系统,消防水泡、水幕、细水雾等。防排烟系统包括:正压送风系统和排烟系统。应急疏散系统包括:应急照明和疏散指示。气体灭火系统包括:二氧化碳灭火系统,七氟丙烷灭火系统、气溶胶灭火系统和IG541等。

The water fire extinguishing system includes indoor fire hydrant system, outdoor fire hydrant system, sprinkler system, fire water bubbles, water curtains, fine water mist, etc. The smoke control system includes a positive pressure air supply system and a smoke exhaust system. The emergency evacuation system includes emergency lighting and evacuation instructions. The gas fire extinguishing system includes: carbon dioxide fire extinguishing system, heptafluoropropane fire extinguishing system, aerosol fire extinguishing system, and IG541, etc.
防火分隔就是防火墙、防火门、防火卷帘的统称。当然还有一些其他小项类似钢结构防火处理、超细干粉等。湿式报警阀调试时,在其试水装置处放水,报警阀应及时动作;水力警铃应发出报警信号,水流指示器应输出报警电信号,压力开关应接通电路报警,并应启动消防水泵。
Fire separation refers to the general term for firewalls, fire doors, and fire shutters. Of course, there are also some other small items such as steel structure fire protection treatment, ultra-fine dry powder, etc. When debugging the wet alarm valve, water should be drained from its water testing device, and the alarm valve should be activated in a timely manner; The hydraulic alarm bell should emit an alarm signal, the water flow indicator should output an alarm electrical signal, the pressure switch should be connected to the circuit for alarm, and the fire pump should be started.
排水装置调试应符合的要求:开启排水装置的主排水阀,应按系统大设计灭火水量做排水试验,并使压力达到稳定。试验过程中,从系统排出的水应全部从室内排水系统排走。
The debugging of drainage devices should meet the following requirements: when opening the main drainage valve of the drainage device, a drainage test should be conducted according to the system's large design fire extinguishing water volume, and the pressure should be stabilized. During the experiment, all water discharged from the system should be drained from the indoor drainage system.
联动试验应符合的要求:采用测试仪表或其它方式,对火灾自动报警系统的各种控测器的输入模拟火灾信号,火灾自动报警控制器发出声光报警信号屏启动自动喷水灭火系统。启动一只喷头或以0.94~1.5L/s的流量从末端试水装置处放水,水流指示器、压力开关、水力警铃和消防水泵等应及时动作并发现相应的信号。
The requirements that the linkage test should meet are: using testing instruments or other methods to simulate fire signals from various controllers of the fire automatic alarm system, the fire automatic alarm controller emits sound and light alarm signals to activate the automatic sprinkler system. Start a nozzle or discharge water from the end water testing device at a flow rate of 0.94-1.5L/s. The water flow indicator, pressure switch, hydraulic alarm bell, and fire pump should be activated in a timely manner and corresponding signals should be detected.
临时高压给水系统,通过启动消防水泵,测量系统不利点试水装置的流量、压力应符合设计要求。当采用市政管网给水系统时,应按高压给水系统或临时高压给水系统的要求进行试验,流量、压力应符合设计要求。
The temporary high-pressure water supply system, by starting the fire pump, measures the flow and pressure of the unfavorable point water testing device in the system, which should meet the design requirements. When using a municipal pipeline water supply system, tests should be conducted according to the requirements of high-pressure water supply systems or temporary high-pressure water supply systems, and the flow rate and pressure should meet the design requirements.