川消_萃联
气体灭火系统
自动喷水灭火系统
当前位置:首页 > 新闻中心火灾自动报警系统之消防控制要点在哪?

火灾自动报警系统之消防控制要点在哪?

来源:https://www.cx-fire.com/ 日期:2026-08-12

1.问题描述

1. Problem description

消防控制室内消防设备布置及安装不符合规范要求。

The layout and installation of fire-fighting equipment in the fire control room do not meet the regulatory requirements.

2.规范要求

2. Standard requirements

《火灾自动报警系统设计规范》(GB 50116-2013)有关规定:

According to the relevant provisions of the Design Code for Automatic Fire Alarm Systems (GB 50116-2013):

3.4.8消防控制室内设备的布置应符合下列规定:

3.4.8 The layout of equipment in the fire control room should comply with the following regulations:

1设备面盘前的操作距离,单列布置时不应小于1.5m;双列布置时不应小于2m。

The operating distance in front of the equipment panel should not be less than 1.5m for single row layout and 2m for double row layout.

2在值班人员经常工作的一面,设备面盘至墙的距离不应小于3m。

隔膜式雨淋阀组

On the side where the on duty personnel often work, the distance from the equipment panel to the wall should not be less than 3m.

3设备面盘后的维修距离不宜小于1m。

The maintenance distance after the equipment is installed should not be less than 1m.

4设备面盘的排列长度大于4m时,其两端应设置宽度不小于1m的通道。

When the arrangement length of the equipment panel is greater than 4m, channels with a width of not less than 1m should be set at both ends.

5与建筑其他弱电系统合用的消防控制室内,消防设备应集中设置,并应与其他设备间有明显间隔。

In the fire control room that is shared with other weak current systems in the building, fire equipment should be centrally installed and clearly separated from other equipment.

6.1.3火灾报警控制器和消防联动控制器安装在墙上时,其主显示屏高度宜为1.5m~1.8m,其靠近门轴的侧面距墙不应小于0.5m,正面操作距离不应小于1.2m。

When installing the fire alarm controller and fire linkage controller on the wall, the height of the main display screen should be 1.5m to 1.8m, and the distance from the side near the door axis to the wall should not be less than 0.5m, and the distance from the front operation should not be less than 1.2m.

《火灾自动报警系统施工及验收标准》(GB 50166-2019)有关规定:

The relevant provisions of the "Construction and Acceptance Standards for Automatic Fire Alarm Systems" (GB 50166-2019):

3.3.1火灾报警控制器、消防联动控制器、火灾显示盘、控制中心监控设备、家用火灾报警控制器、消防电话总机、可燃气体报警控制器、电气火灾监控设备、防火门监控器、消防设备电源监控器、消防控制室图形显示装置、传输设备、消防应急广播控制装置等控制与显示类设备的安装应符合下列规定:

3.3.1 The installation of control and display equipment such as fire alarm controllers, fire linkage controllers, fire display panels, control center monitoring equipment, household fire alarm controllers, fire telephone exchanges, combustible gas alarm controllers, electrical fire monitoring equipment, fire door monitors, fire equipment power monitors, fire control room graphic display devices, transmission equipment, fire emergency broadcast control devices, etc. shall comply with the following regulations:

1应安装牢固,不应倾斜;

1. It should be installed firmly and not tilted;

2安装在轻质墙上时,应采取加固措施;

When installed on lightweight walls, reinforcement measures should be taken;

3落地安装时,其底边宜高出地(楼)面100mm~200mm。

When installing on the ground, its bottom edge should be 100mm to 200mm higher than the ground (floor).

应对措施:

Countermeasures:

1)设计人员应根据消防设备的布置规划与建筑设计专业充分沟通,预留足够的消防控制室面积;

1) Designers should communicate fully with the architectural design profession based on the layout plan of fire equipment, and reserve sufficient fire control room area;

2)应根据选用的产品按相关规范标准进行二次深化设计,做出详细、准确的消防控制室设备布置大样图,施工单位应严格按照设计图纸及规范施工。

2) Secondary detailed design should be carried out according to relevant specifications and standards based on the selected products, and detailed and accurate layout drawings of fire control room equipment should be made. The construction unit should strictly follow the design drawings and specifications for construction.

上一篇:消防联动控制系统的特点是什么?
下一篇:自动喷水灭火系统工作的原理是什么?

相关产品 / Related products