在火灾发生时联动控制器按设定的控制逻辑准确发出联动控制信号给消防泵、喷淋泵、防火门、防火阀、防排烟阀和通风系统等消防设备,完成对灭火系统、疏散诱导系统、防排烟系统及防火卷帘等其他消防有关设备的控制功能,并将动作信号反馈给消防控制室并显示。
When a fire occurs, the linkage controller accurately sends linkage control signals to fire-fighting equipment such as fire pumps, sprinkler pumps, fire doors, fire dampers, smoke exhaust valves, and ventilation systems according to the set control logic, completing the control functions of other fire-fighting related equipment such as fire extinguishing systems, evacuation induction systems, smoke exhaust systems, and fire curtains. The action signals are fed back to the fire control room and displayed.
消防联动控制系统还监视建筑消防设施的运行状态。
The fire linkage control system also monitors the operational status of building fire protection facilities.

系统安装与调试
System installation and debugging
火灾自动报警系统施工安装前,需进行现场检查(检验)和设计符合性检查。
Before the construction and installation of the automatic fire alarm system, on-site inspection (testing) and design compliance check must be carried out.
1)火灾自动报警系统应单独布线,系统内不同电压等级、不同电流类别的线路,不应布在同一管内或线槽的同一槽孔内。
1) The automatic fire alarm system should be wired separately, and the circuits with different voltage levels and current categories in the system should not be arranged in the same pipe or in the same slot of the trunking.
2)导线在管内或线槽内不应有接头或扭结。从接线盒、线槽等处引到探测器底座、控制设备、扬声器的线路,当采用金属软管保护时,其长度不应大于 2m。
2) There should be no joints or twists in the wires inside the conduit or trunking. When using metal hoses for protection, the length of the lines leading from junction boxes, cable trays, etc. to detector bases, control equipment, and speakers should not exceed 2 meters.
3)管路超过下列长度时,应在便于接线处装设接线盒:
3) When the pipeline exceeds the following length, a junction box should be installed at a convenient location for wiring:
①管子长度每超过 30m,无弯曲时。
① When the length of the pipe exceeds 30m without bending.
②管子长度每超过 20m,有1个弯曲时。
② When the length of the pipe exceeds 20m, there is one bend.
③管子长度每超过 10m,有2个弯曲时。
③ When the length of the pipe exceeds 10m and there are 2 bends.
④管子长度每超过 8m,有3个弯曲时。
④ When the length of the pipe exceeds 8m and there are 3 bends.
4)线槽敷设时,应在下列部位设置吊点或支点:
4) When laying cable trays, lifting points or supports should be set up at the following locations:
①线槽始端、终端及接头处。
① At the beginning, end, and joint of the trunking.
②距接线盒 0.2m 处。
② 0.2m away from the junction box.
③线槽转角或分支处。
③ Corner or branch of the trunking.
④直线段不大于 3m 处。
④ The straight line segment is not greater than 3m.
5)火灾自动报警系统导线敷设后,应用 500V 兆欧表测量每个回路导线对地的绝缘电阻,且绝缘电阻值不应小于20MΩ。
5) After laying the wires of the automatic fire alarm system, a 500V megohmmeter should be used to measure the insulation resistance of each circuit wire to ground, and the insulation resistance value should not be less than 20M Ω.
同一工程中的导线,不同用途选择不同颜色加以区分。电源线正出彩应为红色,负出彩应为蓝色或黑色。
The wires in the same project should be distinguished by selecting different colors for different purposes. The positive pole of the power cord should be red, and the negative pole should be blue or black.