剩余电流式探测器负载侧的 N 线不应与其他回路共用,且不能重复接地(不能和 PE 线相连)。

The N line on the load side of the residual current detector should not be shared with other circuits and cannot be repeatedly grounded (cannot be connected to the PE line).

系统工程质量检测判定标准

Quality Inspection and Judgment Standards for System Engineering

系统内的设备及配件规格型号与设计不符、无国家相关证书和检验报告;系统内的任一控制器和火灾探测器无法发出报警信号,无法实现要求的联动功能的,定为 A 类不合格。

The specifications and models of the equipment and accessories in the system do not match the design, and there are no relevant national certificates and inspection reports; If any controller or fire detector in the system cannot issue an alarm signal and cannot achieve the required linkage function, it is classified as Class A unqualified.

检测前提供的资料不符合相关要求的定为 B 类不合格。其余不合格项均为 C 类不合格。系统检测合格判定应为:A=0 且 B≤2,且 B+C≤检查项的 5%为合格,否则为不合格。

If the information provided before testing does not meet the relevant requirements, it will be classified as Class B nonconformity. The remaining non conformities are all Class C non conformities. The system testing qualification judgment should be: A=0 and B ≤ 2, and B+C ≤ 5% of the inspection items to be qualified, otherwise it is unqualified.

年度检测与维修

Annual inspection and maintenance

点型感烟火灾探测器投入运行 2 年后,应每隔 3 年至少全部清洗一遍。

After 2 years of operation, point type smoke fire detectors should be thoroughly cleaned at least every 3 years.

通过采样管采样的吸气式感烟火灾探测器对采样管道进行定期吹洗,非常长的时间间隔不应超过一年;不同类型的探测器应有 10%且不少于 50 只的备品。

The suction type smoke fire detector sampled through the sampling tube should be regularly purged of the sampling pipeline, with a maximum time interval of no more than one year; Different types of detectors should have 10% and no less than 50 spare parts.

常见故障及处理方法

Common faults and their solutions

火灾探测器常见故障

Common faults of fire detectors

1)故障现象。火灾报警控制器发出故障报警,故障指示灯亮,打印机打印探测器故障类型、时间、部位等。

1) Fault phenomenon. The fire alarm controller issues a fault alarm, the fault indicator light is on, and the printer prints the type, time, and location of the detector fault.

2)故障原因。探测器与底座脱落、接触不良;报警总线与底座接触不良;报警总线开路或接地性能不良造成短路;探测器本身损坏;探测器接口板故障。

2) Reason for malfunction. The detector is detached from the base and has poor contact; Poor contact between the alarm bus and the base; Short circuit caused by open circuit or poor grounding performance of the alarm bus; The detector itself is damaged; Detector interface board malfunction.

隔膜式雨淋阀组

3)排除方法。重新拧紧探测器或提升底座与探测器卡簧的接触面积;重新压接总线,使之与底座有良好接触;查出有故障的总线位置,予以更换;更换探测器;维修或更换接口板。

3) Exclusion method. Re tighten the detector or increase the contact area between the base and the detector clamp spring; Reconnect the bus to ensure good contact with the base; Identify the faulty bus location and replace it; Replace the detector; Repair or replace the interface board.

年度检测与维修

Annual inspection and maintenance

各类消防用电设备、主备电源自动转换装置,应进行3次转换信号,每次均正常。

All types of fire-fighting electrical equipment and automatic conversion devices for main and backup power sources should undergo three signal conversions, and each conversion should be normal.

图片

Image

火灾报警控制器

Fire alarm controller

①实际安装台数 5 台以下,全部检验

① If the actual number of installed units is less than 5, all shall be inspected

②6-10 台,抽检 5 台

② 6-10 units, randomly inspect 5 units

③实际安装超过 10 台,按实际安转数量 30-50%的比例抽检,不少于 5 台火灾探测器

③ If the actual installation exceeds 10 units, a random inspection shall be conducted at a ratio of 30-50% of the actual installation quantity, with no less than 5 fire detectors

④实际安装台数 100 台以下,检验 20 只(每个回路都应抽检)

④ If the actual installation quantity is less than 100 units, 20 units should be inspected (each circuit should be sampled)

⑤实际安装超过 100 台,按实际安转数量 10-20%的比例抽检,不少于 20 台

⑤ If the actual installation exceeds 100 units, a random inspection shall be conducted based on 10-20% of the actual installation quantity, with no less than 20 units

室内消火栓

indoor fire hydrant

①控制室操作启停 1-3 次

① Control room operation start stop 1-3 times

②操作消火栓的按钮,按实际安转数量 5-10%比例抽检自动喷水系统

② Operate the button of the fire hydrant and randomly inspect the automatic sprinkler system at a ratio of 5-10% of the actual installation quantity

③控制室操作启停 1-3 次

③ Control room operation start stop 1-3 times

④水流指示器、信号阀等按照实际安装数量 30-50%比例抽检

④ Water flow indicators, signal valves, etc. shall be randomly inspected at a ratio of 30-50% of the actual installation quantity

⑤压力开关、电动阀、电磁阀等全数检查

⑤ Inspect all pressure switches, electric valves, solenoid valves, etc

⑥卷帘门5樘以下,全数检查,超过5樘按实际 20%抽检,总数不少于5樘

⑥ If there are less than 5 rolling shutter doors, all of them shall be inspected. If there are more than 5 doors, 20% of them shall be randomly inspected, and the total number shall not be less than 5 doors

上一篇:火灾自动报警系统误报的原因