泵房自动启泵那几秒

来源:https://www.cx-fire.com/ 日期:2026-11-27

火灾里非常怕的不是没水,是“该出水时泵没起来”。消防泵组平时安静待机,真到喷淋爆头、消火栓拉开的那一刻,控制柜能不能在几秒内把主泵顶上去,决定的是整栋楼的命运。泵房这事,验收时看铭牌,运行时看逻辑。

The biggest fear in a fire is not the lack of water, but the pump not starting when it's time to release water. The fire pump unit is usually quiet and standby, but at the moment when the sprinkler head bursts and the fire hydrant is pulled open, whether the control cabinet can lift the main pump up within a few seconds determines the fate of the entire building. Regarding the pump room, check the nameplate during acceptance and the logic during operation.

流量别只算消火栓

Don't just count traffic as fire hydrants

气体灭火

很多泵房选型翻车,是把消火栓流量和喷淋流量分开报,非常后共用一组泵时没叠加。按 GB50974-2014,共用消防给水系统的工作泵,流量要同时覆盖非常不利点消火栓与自动喷水非常不利点喷头之和;扬程要从消防水池非常低水位量到非常远喷头/栓口,加管损、加报警阀附件损失、加非常不利点所需压力,再留 5%–10% 余量往上靠标准档。

Many pump rooms choose to overturn by reporting the flow rates of fire hydrants and sprinklers separately, and when sharing a set of pumps, they are not stacked. According to GB50974-2014, the working pump of the shared fire water supply system should have a flow rate that covers both the most unfavorable point of the fire hydrant and the most unfavorable point of the automatic sprinkler nozzle; The lift should be from the lowest water level of the fire water tank to the farthest nozzle/hydrant, with pipe damage, loss of alarm valve accessories, and the required pressure at the most unfavorable point, leaving a margin of 5% -10% upward towards the standard range.

零流量压力别超设计工作压力 140%,否则低流量工况下密封、振动全出问题;出流量到设计值 150% 时,出口压力仍不能低于设计值 65%。

Zero flow pressure should not exceed the design working pressure by 140%, otherwise sealing and vibration problems will occur under low flow conditions; When the outflow reaches 150% of the design value, the outlet pressure cannot be lower than 65% of the design value.

控制柜建议留机械应急

The control cabinet must be equipped with mechanical emergency equipment

自动启泵走压力开关/流量开关/联动信号,但控制线路一断,自动就废了。规范要求控制柜带机械应急启泵功能,有权限的人手动合闸,报警后 5 分钟内泵要转起来。 泵房平时建议打在“自动”位,巡检表上那一栏“主备切换开关位置”不是形式,是保命项。

Automatically start the pump and send the pressure switch/flow switch/linkage signal, but once the control circuit is disconnected, the automatic system will be disabled. The standard requires the control cabinet to have a mechanical emergency pump start function, and authorized personnel should manually close the switch. The pump should start within 5 minutes after the alarm. The pump room must usually be set to the "automatic" position, and the column "main/backup switch position" on the inspection form is not a formal item, but a life-saving item.

一用一备不是摆设

One for use and one for backup are not decorations

工作泵和备用泵能力应相等,主泵故障备用泵自动投;高层或大体量公建常做两用一备。别用“一台泵轮换带多台”的省事接法,也别把稳压泵当主泵用——稳压泵是小流量高扬程保压力的,火灾时主泵才是供水主力。

The capacity of the working pump and the standby pump should be equal, and the standby pump will automatically start when the main pump fails; High rise or large-scale public buildings often have two uses and one backup. Don't use the convenient method of "one pump rotating with multiple", and don't use the stabilizing pump as the main pump - stabilizing pumps are small flow high head pressure maintaining pumps, and the main pump is the main water supply in case of a fire.

月度试机看四样

Monthly test run to see four samples

每月手动启泵跑 5–10 分钟,听异响、看振动、测电流压力、查机械密封漏不漏;每季度做主备切换和自动启泵联动;每年校压力表、压力开关,清入口过滤器,测性能曲线。 泵组常见故障就那几条:不来泵查压力开关设定和控制柜接线,噪音大查汽蚀和轴承,流量不够查叶轮磨损、入口堵塞、转向反了。

Manually start the pump and run it for 5-10 minutes every month, listen for abnormal noises, observe vibrations, measure current and pressure, and check if the mechanical seal is leaking; Quarterly switching between primary and backup and automatic pump start linkage; Every year, calibrate the pressure gauge, pressure switch, clean the inlet filter, and measure the performance curve. There are only a few common faults with the pump unit: checking the pressure switch setting and control cabinet wiring for failure to come to the pump, checking for cavitation and bearings for high noise, checking for impeller wear, inlet blockage, and reverse steering for insufficient flow.

末端试水是泵的体检口

The end water test is the inspection port of the pump

每个报警阀组非常不利点装末端试水装置,放水时出水压力不低于 0.05MPa,从放水到水泵启动不超 5 分钟;自动启泵工况下消防泵 55 秒内投入正常运行。 这一放,压力开关、报警阀、水力警铃、主泵链路全串一遍,比看台账管用。

Each alarm valve group shall be equipped with an end water testing device at the most unfavorable point, and the outlet pressure shall not be less than 0.05 MPa during water discharge. The time from water discharge to pump start-up shall not exceed 5 minutes; The fire pump is put into normal operation within 55 seconds under automatic pump start condition. In this case, the pressure switch, alarm valve, hydraulic alarm bell, and main pump link are all connected in series, which is more effective than checking the ledger.

泵房不炫技,就三件事:流量扬程算对、控制柜留机械应急、每月真启一次。算错了验收过不了,不启泵真着火全白搭。

If the pump room doesn't show off its skills, there are only three things: calculating the flow and head correctly, keeping mechanical emergency in the control cabinet, and starting it once a month. If the calculation is wrong, the acceptance cannot be passed. If the pump does not start and catches fire, it will be completely useless.

本文由川消友情奉献.更多有关的知识请点击:http://www.cx-fire.com我们将会对你提出的疑问进行详细的解答,欢迎你登录网站留言.

This article is dedicated by Chuanxiao Friendship For more information, please click: http://www.cx-fire.com We will provide detailed answers to your questions. You are welcome to log in to our website and leave a message