川消_萃联
气体灭火系统
自动喷水灭火系统
当前位置:首页 > 新闻中心关于消防泵现场调试的一些知识和建议

关于消防泵现场调试的一些知识和建议

来源:http://www.cx-fire.com/ 日期:2023-05-24

消防泵场景的应用非常常见,广泛应用在各种工业领域,但在实际调试应用的时候,经常遇到一些问题,下面川消小编向大家分享关于消防泵现场调试的一些知识和建议。
The application of the fire pump scene is very common and widely used in various industrial fields. However, some problems are often encountered in the actual commissioning application. Now, Chuanxiao Xiaobian will share some knowledge and suggestions about the on-site commissioning of fire pump.
水泵方面
In terms of water pumps
1.检查水池水位,是否高过水泵进水口(低位水池除外,但需加装底)。
1. Check whether the water level in the water tank is higher than the water inlet of the water pump (except for the low level water tank, which needs to be installed with a bottom).
2.检查进水管路,是否内有异物(如焊渣类)拆开泵与管路连接处,放水冲洗。
2. Check the water inlet pipeline for any foreign objects (such as welding slag). Remove the connection between the pump and the pipeline and discharge water for flushing.
3.打开水泵进出口门,旋下水泵进出口法兰上的排气螺丝,排净泵腔内空气,水出为止。
3. Open the inlet and outlet valves of the water pump, unscrew the exhaust screws on the inlet and outlet flanges of the water pump, and exhaust the air in the pump chamber until the water is discharged.
4.拆下水泵电机防护罩,用手扳动风叶,检查水泵转动是否灵活。
4. Remove the protective cover of the water pump motor, pull the fan blades by hand, and check whether the water pump rotates flexibly.
5.检查电源接线方面是否牢固,是否。
5. Check if the power wiring is secure and safe.
控制柜方面
In terms of control cabinet
检查控制柜外观是否损坏,内部螺丝是否松动。
Check whether the appearance of the control cabinet is damaged and whether the internal screws are loose.
按线路图接好电源线,用仪表检查是否缺相,电压是否正常。
Connect the power cord according to the circuit diagram, and use an instrument to check for phase loss and normal voltage.
水泵暂时不接情况下,按手动启动按钮重复几次,看接触器是否吸合正常。
When the water pump is temporarily disconnected, press the manual start button several times to check if the contactor is working properly.
川消
接上水泵电源线,点动(启动后即停)看水泵转向是否正常(正常为顺时针旋转)。
Connect the power cord of the water pump and jog (stop after starting) to check if the water pump rotates normally (clockwise rotation is normal).
如反转,水泵电源线任意两根线互调。
If reversed, any two lines of the water pump power line will be mutually adjustable.
按控制柜内部门上的线路图高、中、低位置,接电接点压力表。控制柜调为自动,测试压力表。如压力表不会停止或启动,立即检查信号线是否接反或其他。
Connect the electrical contact pressure gauge to the high, medium, and low positions on the internal door of the control cabinet according to the wiring diagram. Set the control cabinet to automatic and test the pressure gauge. If the pressure gauge does not stop or start, immediately check if the signal wire is connected in the wrong direction or otherwise.
注意事项
matters needing attention
·严禁水泵内无水运转,容易损坏机封。
·It is strictly prohibited to operate the water pump without water, as it may damage the machine seal.
·严格按照控制柜内线路图接线,严禁改动控制路线。
·Strictly follow the wiring diagram inside the control cabinet and strictly prohibit changing the control route.
·以上有未尽之处,请人士规范操作。
·If there are any areas that are not covered above, please have professional personnel operate them in a standardized manner.
关于消防泵现场调试的一些知识和建议相关内容就讲解到这里了,希望能够给您好的帮助,更多事项就来我们网站http://www.cx-fire.com咨询!
This is the end of some knowledge and suggestions on the on-site commissioning of fire pump. I hope it can help you. More information can be found on our website http://www.cx-fire.com consulting service
上一篇:七氟丙烷气体灭火系统维护保养存在的问题
下一篇:自动跟踪定位射流灭火系统应符合这样的要求!

相关产品 / Related products