消防信号蝶阀阀门漏水壳体破裂什么原因?
来源:http://www.cx-fire.com/ 日期:2022-07-01
阀门漏水
Water leakage of valve
消防信号蝶阀是按照标准GB5135.6-2003生产的,是公安部规定的强制性检验产品。根据标准要求,消防信号蝶阀的额定工作压力应不低于1.2MPa,并应??能承受2倍额定工作压力的静水压力5min。试验时蝶阀的密封处不应有泄漏。我们公司是一家比较正规的企业。为了对产品和用户负责,每个信号蝶阀出厂前必须100%密封,检测合格后方可入库。
The fire signal butterfly valve is produced according to the national standard gb5135.6-2003 and is a compulsory inspection product stipulated by the Ministry of public security. According to the standard requirements, the rated working pressure of the fire signal butterfly valve should not be less than 1.2MPa, and should be?? It can withstand hydrostatic pressure twice the rated working pressure for 5min. There should be no leakage at the sealing part of the butterfly valve during the test. Our company is a relatively formal enterprise. In order to be responsible for the products and users, each signal butterfly valve must be 100% sealed before leaving the factory, and can only be warehoused after passing the inspection.
如果水质不符合要求,阀门上有杂质或施工残留杂质,造成阀门不能正常关闭,肯定会出现漏水问题,可以通过冲洗。
If the water quality does not meet the requirements, there are impurities or construction residual impurities on the valve, causing the valve to not close normally, there will certainly be water leakage, which can be solved by flushing.
川消小编认为,如果施工不小心,会导致蝶阀两端连接管的同心度出现偏差,也会导致蝶阀不能正常关闭,造成泄漏。施工人员可以在安装管道前重新调整管道的同心度。
Chuanxiao Xiaobian believes that if the construction is not careful, the concentricity of the connecting pipes at both ends of the butterfly valve will deviate, and the butterfly valve will not close normally, resulting in leakage. The construction personnel can readjust the concentricity of the pipeline before installing it.

破裂的阀壳
Cracked valve casing
在项目中,偶尔有用户反映消防信号蝶阀外壳破裂,无法升压或外漏,这种情况并不多。毫无疑问,这种情况只能在运输过程中,或者在搬运、储存、施工、安装等环节中,才能判断为可能。由于消防蝶阀一般安装在离地较高的建筑物的平屋顶下,如果施工人员不慎跌落或野蛮搬运,信号蝶阀外壳就会破裂。材料比较脆,容易折断,所以一定要轻拿轻放,轻拿轻放。
In the project, there are occasional users who report that the shell of the fire signal butterfly valve is broken, unable to boost pressure or leakage, which is not very common. There is no doubt that this situation can only be judged as possible in the transportation process, or in the handling, storage, construction, installation and other links. Since the fire butterfly valve is generally installed under the flat roof of buildings higher from the ground, if the construction personnel accidentally fall or rough handling, the shell of the signal butterfly valve will break. The material is brittle and easy to break, so you must handle it with care.
确认阀体破损后,阀门报废,只能更换。当然,责任方应承担相应的费用。
After confirming that the valve body is damaged, the valve is scrapped and can only be replaced. Of course, the responsible party should bear the corresponding costs.
Through the above article, you can clearly understand the content of the problem. I believe that after reading this article, you can have a deeper understanding of this product. If you want to know more in the future, you can continue to follow our official website http://www.cx-fire.com , please feel free to contact us if necessary.