消防泵说白了,消防上放的泵,但对消防事业很是重要,所以说全部日常的维护保养与养护也是不可有违的。那么消防泵安装的具体步骤是怎样的?
Fire pump to put it bluntly, fire safety on the pump, but it is very important to the fire cause, so all the daily maintenance and maintenance can not be violated. What are the specific steps of fire pump installation?
1、消防泵安装前应检查产品合格证的强度,其规格、型号、规格、功能应符合设计规定,并按安装说明书进行安装;
1. Before the installation of the fire pump, the strength of the product certificate shall be checked, and its specification, model, specification and function shall comply with the design regulations, and the installation shall be carried out according to the installation instructions;
2、消防泵安装前,应检查离心泵基础混凝土的强度、减振装置、坐标、设计标高、地脚螺栓孔的规格及位置;
2. Before the installation of the fire pump, the strength of the foundation concrete of the centrifugal pump, the damping device, the coordinates, the design elevation, and the specification and position of the anchor bolt hole should be checked;
3、安装消防泵前,川消小编建议您应检查消防泵的中部,以及消防泵与墙壁或其他设施的间距,并应符合安装、运行和防护监督的要求;
3. Before installing the fire pump, Chuanxiao Xiaobian suggests that you should check the middle of the fire pump and the distance between the fire pump and the wall or other facilities, and should meet the requirements of installation, operation and protection supervision;
4、消防泵吸湿管上的调节阀应在消防泵固定在底座后安装。其直径不应小于消防泵吸湿口的直径,不应使用无可靠锁紧装置的调节阀。宜选用沟式或对夹式止回阀闸阀;
4. The regulating valve on the hygroscopic pipe of the fire pump shall be installed after the fire pump is fixed on the base. Its diameter should not be less than the diameter of the hygroscopic port of the fire pump, and the regulating valve without a reliable locking device should not be used. Groove or wafer check valve gate valve should be selected;
川消
5、当消防泵和消防水库位于两个独立的底座并相互刚性连接时,吸湿管应配备柔性连接管;
5. When the fire pump and the fire reservoir are located on two independent bases and rigidly connected with each other, the moisture absorption pipe shall be equipped with flexible connecting pipe;
6、吸湿管水平管段不应有气体和蒸汽泄漏。大小头连接时,应选用偏心异径管件,并冲洗管顶;
6. There should be no gas and steam leakage in the horizontal pipe section of the moisture absorption pipe. When connecting large and small heads, eccentric reducing pipe fittings should be selected, and the pipe top should be flushed;
7、消防泵出水口应安装消声止回阀、调节阀和气压表;系统软件主出水口还应安装气压表和压力控制器;安装气压表时应加缓冲装置。气压表与缓冲装置之间应安装旋塞阀;如果设计方案中没有规定压力表的量程,则应为系统软件压力的2倍左右;
7. Silencing check valve, regulating valve and barometer shall be installed at the outlet of fire pump; The main water outlet of the system software shall also be equipped with a barometer and a pressure controller; Buffer device shall be added when installing barometer. A plug valve should be installed between the barometer and the buffer device; If the range of the pressure gauge is not specified in the design scheme, it should be about twice the pressure of the system software;
8、川消消防泵减振装置及进水口软接头的安装应符合设计要求,并应有产品介绍及安装说明。
8. The installation of vibration damping device and water inlet soft joint of Chuanxiao fire pump shall meet the design requirements, and there shall be product introduction and installation instructions.
消防泵广泛运用于环境保护、污水处理、消防等单位,而其种类都相似的,仅仅一致和数据流量有不一样,所以消防泵在安装时要符合规定,以上就是相关内容了,有疑问就来关注网站http://www.cx-fire.com联系我们吧!
Fire pumps are widely used in environmental protection, sewage treatment, fire safety and other units, and their types are similar, only consistent and different from the data flow, so the installation of fire pumps should comply with the regulations. The above is the relevant content. If you have any questions, please pay attention to the website http://www.cx-fire.com Contact us!