控制川消七氟丙烷检测灭火系统有三种方法
来源:http://www.cx-fire.com/ 日期:2023-02-17
七氟丙烷检测灭火系统工作前提是电磁驱动装置装有齿轮,目的是防止运输、安装、调试过程中的碰撞、震动导致闸门失灵。安装在现场后,使用前必须拔掉齿轮,否则阀门不会打开。下面
川消小编来讲讲控制七氟丙烷检测灭火系统有什么方法。
The working premise of heptafluoropropane detection and fire extinguishing system is that the electromagnetic drive device is equipped with gears to prevent collision and vibration during transportation, installation and commissioning from causing gate failure. After installation on site, the safety gear must be pulled out before use, otherwise the valve will not open. Now let's talk about the methods of controlling the heptafluoropropane detection and fire extinguishing system.
1.自动控制方法:控制器将控制方法选择开关置于“自动”位置时,灭火装置处于自动控制状态。
1. Automatic control method: When the controller sets the control method selection switch to the "automatic" position, the fire extinguishing device is in automatic control state.
如果只有一个探测器发出火灾信号,控制器就会发出异常的声音信号,不启动灭火装置,通知出现异常情况。当两个探测器同时发出火灾信号时,探测器会发出火灾圣光警报,通知火灾发生。向相关人员撤离现场,向控制中心发送火灾信号,向控制器发出联动指令,关闭风机、防火阀等联动设备,延迟30秒后发出灭火指令,启动电磁驱动装置,释放灭火剂,释放灭火剂,实施出入口放气指示灯为了防止传感器误操作引起的灭火剂释放,或者火灾小值班人员可以自行消灭,在警报过程中发现不需要打开灭火器的情况,或者按手动控制箱内或控制器的紧急停止按钮,防止控制器灭火指令的发生,为了避免灭火器启动,避免造成不必要的浪费和混乱。
If only one detector sends out a fire signal, the controller will send out an abnormal sound signal, and the fire extinguishing device will not be started to notify the abnormal situation. When two detectors send out fire signals at the same time, the detector will send out a fire holy light alarm to notify the fire. Evacuate relevant personnel from the site, send fire signals to the control center, send linkage commands to the controller, shut down the fan, fire damper and other linkage equipment, send out the fire extinguishing command after a delay of 30 seconds, start the electromagnetic drive device, release the fire extinguishing agent, release the fire extinguishing agent, and implement the vent indicator at the entrance and exit to prevent the release of the fire extinguishing agent caused by the misoperation of the sensor, or the personnel on duty can eliminate the fire by themselves, In the process of alarm, it is found that it is not necessary to open the fire extinguisher, or press the emergency stop button in the manual control box or controller to prevent the occurrence of the controller fire extinguishing command, in order to prevent the fire extinguisher from starting and causing unnecessary waste and confusion.

2.电被动控制方法:选择控制器的控制方法。
2. Electric passive control method: select the control method of the controller.
将开路磁力置于“被动”位置时,灭火装置处于电被动控制状态。在这种控制方式中,探测器发送火灾信号时,控制器发出火灾声音警报,但灭火器不启动。工作人员可以按“紧急启动”按钮启动灭火器来扑灭火灾。每个保护区入口和控制主机面板都有紧急启动按钮。如果确认保护区着火,可以在入口按紧急启动按钮,或按控制器面板上的紧急启动按钮来灭火。
When the open-circuit magnetic force is placed in the "passive" position, the fire extinguishing device is in the electrically passive control state. In this control mode, when the detector sends a fire signal, the controller sends an audible fire alarm, but the fire extinguisher does not start. The staff can press the "emergency start" button to start the fire extinguisher to put out the fire. There are emergency start buttons at the entrance of each protection zone and on the control host panel. If it is confirmed that the protection area is on fire, press the emergency start button at the entrance or press the emergency start button on the controller panel to put out the fire.
3.机械紧急手动控制方法:
3. Mechanical emergency manual control method:
控制系统发生故障时,通过机械紧急手动启动灭火器灭火。
In case of failure of the control system, the fire extinguisher shall be started manually through mechanical emergency.
There are three ways to control the fire detection and extinguishing system of Chuanxiao Heptafluoropropane. The above is the answer to the question. What doubts or needs do you have about this? Welcome to our website http://www.cx-fire.com Get to know!