川消消防软管卷盘和轻便消防水龙是控制建筑物内固体可燃物初起火的有效器材,用水量小、配备和使用方便,适用于非专门人员使用扑灭初起火势。
Chuanxiao fire hose reel and portable fire hose are effective equipment to control the initial fire of solid combustible materials in the building, with small water consumption, easy to equip and use, and are suitable for non-specialized personnel to put out the initial fire.
设置要求
Setting requirements
1.《建设设计防火规范》第8.2.1条未规定的建筑或场所和符合第8.2.1条规定的下列建筑或场所,可不设置室内消火栓系统,但宜设置消防软管卷盘或轻便消防水龙:
1. The buildings or places not specified in Article 8.2.1 of the Code for Fire Protection Design of Buildings and the following buildings or places that comply with Article 8.2.1 may not be equipped with indoor fire hydrant system, but fire hose reels or portable fire hoses should be installed:
1)耐火等级为一、二级且可燃物较少的单、多层丁、戊类厂房(仓库)。
1) Single and multi-storey Class D and E plants (warehouses) with fire resistance rating of Class I and II and less combustible materials.
2)耐火等级为三、四级且建筑体积不大于3000m?的丁类厂房;耐火等级为三、四级且建筑体积不大于5000m?的戊类厂房(仓库)。
2) The fire resistance rating is Class III and IV and the building volume is not more than 3000m? Class D plant; The fire resistance rating is Class III and IV and the building volume is not more than 5000m? Class E plant (warehouse).
3)粮食仓库、金库、远离城镇且无人值班的独立建筑。
3) Grain warehouse, treasury, independent buildings away from towns and unattended.
4)存有与水接触能引起燃烧爆炸的物品的建筑。
4) A building containing objects that can cause combustion and explosion in contact with water.
川消
5)室内无生产、生活给水管道,室外消防用水取自储水池且建筑体积不大于5000m?的其他建筑。
5) There is no production and domestic water supply pipeline in the room, and the outdoor fire water is taken from the storage tank, and the building volume is not more than 5000m? Other buildings.
2.人员密集的公共建筑、建筑高度大于100m的建筑和建筑面积大于200m?的商业服务网点内应设置消防软管卷盘或轻便消防水龙。高层住宅建筑的户内宜配置轻便消防水龙。
2. Public buildings with dense personnel, buildings with building height greater than 100m and building area greater than 200m? Fire hose reels or portable fire hoses shall be installed in the commercial service outlets of. Portable fire hoses should be equipped indoors in high-rise residential buildings.
3.老年人照料设施内应设置与室内供水系统直接连接的消防软管卷盘,消防软管卷盘的设置间距不应大于30.0m。
3. Fire hose reels directly connected to the indoor water supply system shall be set in the elderly care facilities, and the distance between fire hose reels shall not be greater than 30.0m.
安装要求
Installation requirements
1.消防软管卷盘应配置内径不小于ф19的消防软管,其长度宜为30.0m;轻便水龙应配置公称直径25有内衬里的消防水带,长度宜为30.0m;
1. The fire hose reel shall be equipped with an inner diameter not less than ф 19. The length of fire hose should be 30.0m; Portable faucets shall be equipped with fire hose with inner lining with nominal diameter of 25, and the length should be 30.0m;
2.同一建筑物内设置消防软管卷盘和轻便水龙应采用统一规格的配件;
2. The fire hose reels and portable faucets set in the same building shall adopt the fittings of uniform specifications;
3.消防软管卷盘和轻便水龙应设置明显的性固定标志。
3. Fire hose reels and portable hoses shall be provided with obvious permanent fixed signs.
消防软管卷盘使用简单、方便,无需经过培训,一般人员均可使用,是扑灭初期火灾的有效快捷措施,特别是三小场所、出租屋等未设置室内消火栓系统的场所建议设置消防软管卷盘。更多相关内容就来我们网站http://www.cx-fire.com咨询!
The fire hose reel is simple and convenient to use, and can be used by ordinary personnel without training. It is an effective and quick measure to put out the initial fire. Especially, it is recommended to set the fire hose reel in places without indoor fire hydrant system, such as three small places and rental houses. Come to our website for more relevant content http://www.cx-fire.com consulting service