The installation of outdoor fire hydrants should be clearly visible and easy to detect, making it convenient for water outlet operations. Underground fire hydrants should also have clear and fixed signs near the ground. The above ground fire hydrant is selected for installation on warm climates, and the basement is selected for installation on cold climates. Do you know how many meters should the distance between outdoor fire hydrants not exceed? Below, the editor of Chuanxiao will analyze for you:
1、当建筑物在市政消火栓保护半径150m以内,且消防用水量不超过15L/s时,可不设室外消火栓。
1. When the building is within a radius of 150m of municipal fire hydrant protection and the fire water consumption does not exceed 15L/s, outdoor fire hydrants may not be installed.
2、室外消火栓应沿高层建筑周围均匀布置,并不宜集中在建筑物一侧。
2. Outdoor fire hydrants should be evenly arranged around high-rise buildings and should not be concentrated on one side of the building.
3、人防工程室外消防栓距人防工程入口不宜小于5m。
3. The distance between the outdoor fire hydrant of the civil air defense project and the entrance of the civil air defense project should not be less than 5m.
4、停车场的室外消防栓宜沿停车场周边设置,且距离近一排汽车不宜小于7m,距加油站或库不宜小于15m。
4. The outdoor fire hydrants in the parking lot should be set along the perimeter of the parking lot, and should not be less than 7m from the nearest row of cars, and should not be less than 15m from the gas station or garage.
5、室外消防栓应设置在便于消防车使用的地点。
5. Outdoor fire hydrants should be located in locations that are convenient for fire trucks to use.
川消
6、室外消防栓宜采用地上式,当采用地下式消火栓时,应有明显标志。寒冷地区采用地下式,非寒冷地区宜采用地上式,地上式有条件可采用防撞型。
6. Outdoor fire hydrants should be of the above ground type, and when underground fire hydrants are used, there should be clear signs. Underground type is used in cold areas, while above ground type is recommended in non cold areas. If conditions permit, anti-collision type can be used for above ground type.
7、室外地上式消防栓应有一个直径为150mm或100mm和两个直径为65mm的栓口。室外地下式消火栓应有直径为100和65mm的栓口各一个。
7. Outdoor aboveground fire hydrants should have one diameter of 150mm or 100mm and two diameter of 65mm. Outdoor underground fire hydrants should have one hydrant mouth with a diameter of 100 and one hydrant mouth with a diameter of 65mm.
8、室外消防栓的保护半径不应超过150m,间距不应超过120m。
8. The protection radius of outdoor fire hydrants should not exceed 150m, and the spacing should not exceed 120m.
9、室外消防栓距路边不应超过2m,距房屋外墙不宜小于5m。
9. The outdoor fire hydrant should not exceed 2m from the roadside and should not be less than 5m from the exterior wall of the house.