1、泵组连接处有渗漏
1. Leakage at the connection of the pump unit
(1)故障原因分析:连接件松动;连接处O 型圈或密封垫损坏;连接件损坏。
(1) Fault cause analysis: loose connectors; Damaged O-ring or sealing gasket at the connection; Damaged connectors.
(2)故障处理:拧紧连接件;更换O型圈或密封垫;更换连接件。
(2) Fault handling: Tighten the connectors; Replace the O-ring or sealing gasket; Replace the connector.
2、泵组出口压力低
2. Low outlet pressure of pump unit
(1)故障原因分析:泵组测试阀未关闭;泵组进线电源反相;高压泵损坏;使用流量超出额定值。
(1) Fault cause analysis: The testing valve of the pump unit was not closed; The power supply of the pump unit inlet is in reverse phase; High pressure pump damaged; The usage flow exceeds the rated value.
(2)故障处理:关闭泵组测试阀;调整进线电源相序;更换高压泵;在泵组额定值内工作。
(2) Fault handling: Close the pump unit test valve; Adjust the phase sequence of the incoming power supply; Replace the high-pressure pump; Working within the rated value of the pump set.
川消
3、川消泵组不启动
3. Chuanxiao pump group does not start
(1)故障原因分析:高压泵接触器未闭合;泵组停止触点断开;LOGO!未执行程序;电源未接通;断水水位保护。
(1) Fault cause analysis: The high-pressure pump contactor is not closed; The pump unit stop contact is disconnected; LOGO! Not executing the program; The power supply is not connected; Water cut-off level protection.
(2)故障处理:闭合接触器;闭合泵组停止触点;检修LOGO!必要时更换;接通电源;恢复调节水箱水位。
(2) Fault handling: Close the contactor; Close the pump unit stop contact; Repair the logo! Replace if necessary; Connect the power supply; Restore the water level of the regulating water tank.
4、稳压泵频繁启动
4. Frequent start-up of pressure stabilizing pump
(1)故障原因分析:管道有渗漏;泄压阀密封不好;测试阀未关紧;单向阀密封垫上粘连杂质。
(1) Fault cause analysis: There is leakage in the pipeline; Poor sealing of safety relief valve; The test valve is not tightly closed; Adhesive impurities on the sealing gasket of the one-way valve.
(2)故障处理:管道渗漏点补漏;检修泄压阀;完全关闭测试阀;清洗单向阀并清洁水箱及管道。
(2) Fault handling: repairing pipeline leakage points; Maintain the safety relief valve; Fully close the test valve; Clean the one-way valve and clean the water tank and pipelines.
5、稳压泵规定时间内不能恢复压力
5. The regulated pump cannot restore pressure within the specified time
(1)故障原因分析:管道内残存空气;管道有渗漏;高压球阀渗漏;稳压泵出口压力低;稳压泵损坏。
(1) Fault cause analysis: residual air in the pipeline; There is leakage in the pipeline; Leakage of high-pressure ball valve; Low outlet pressure of the pressure stabilizing pump; The pressure stabilizing pump is damaged.
(2)故障处理:完全排除管道空气;管道渗漏点补漏;见下文高压球阀渗漏故障处理方法;调节稳压泵压力调节螺丝;更换稳压泵。
(2) Fault handling: completely eliminate the air in the pipeline; Pipeline leakage point repair; Refer to the following methods for handling leakage faults of high-pressure ball valves; Adjust the pressure regulating screw of the stabilizing pump; Replace the pressure stabilizing pump.