1.主消防控制室的消防设备能够对
1. The fire protection equipment in the main fire control room can
系统内共用消防设备进行控制,显示其状态信息,并能够显示各个分消防控制室内消防设备的状态信息,具备
The system shares fire equipment for control, displays its status information, and can display the status information of fire equipment in each sub fire control room
对消防控制室内消防设备及其所控制的消防系统、设备的控制功能。
The control function of the fire equipment in the fire control room and the fire system and equipment it controls.
2.各个分消防控制室的消防设备之间,可以互相传输、显示状态信息,不能互相控制消防设备。
2. The fire equipment in each sub fire control room can transmit and display status information to each other, but cannot control each other's fire equipment.
3.消防控制室内设置的消防设备应能监控并显示建筑消防设施运行状态信息,并应具有向城市消防远程监控中心传输信息的功能。
3. The fire equipment installed in the fire control room should be able to monitor and display the operational status information of building fire protection facilities, and should have the function of transmitting information to the urban fire remote monitoring center.
川消
4.消防控制室的供电,应在其配电线路的末一级配电箱处设置自动切换装置。
4. For the power supply of the fire control room, an automatic switching device should be installed at the last level distribution box of its distribution line.
5.消防控制室以及发生火灾时仍需正常工作的消防设备房应设置备用照明,其作业面的低照度不应低于正
5. Backup lighting should be installed in the fire control room and the fire equipment room that still needs to work normally in the event of a fire, and the minimum illumination on the working surface should not be lower than positive
常照明的照度。
The illuminance of regular lighting.
6.设置火灾自动报警系统和需要联动控制的消防设备的建筑(群)应设置消防控制室。
6. Buildings (clusters) with automatic fire alarm systems and fire equipment that require linkage control should be equipped with fire control rooms.
7.附设在建筑内的消防控制室应采用耐火极限不低于2.00h的防火隔墙和1.50h的楼板与其他部位分隔。消防控制室开向建筑内的门应采用乙级防火门。
7. The fire control room attached to the building should be separated from other parts by a fire partition wall with a fire resistance limit of no less than 2.00h and a 1.50h floor slab. The doors in the fire control room that open into the building should use Class B fire doors.
8.附设在汽车库、修车库内的消防控制室应采用防火隔墙和耐火极限不低于1.50h的不燃性楼板相互隔开或与相邻部位分隔。
8. The fire control room attached to the garage and repair garage should be separated from each other or adjacent parts by fire partition walls and non combustible floor slabs with a fire resistance limit of not less than 1.50 hours.