川消消防控制器的链接需要注意什么?
来源:http://www.cx-fire.com/ 日期:2022-05-01
对消防火灾报警控制器进行自检功能检查。
Check the self inspection function of the fire alarm controller.
对可测量相关参数进行查看和记录,如回路电流等。
Check and record relevant measurable parameters, such as loop current, etc.
公共场所烟感器、温感器安装检查,与底座接触是否良好,外观是否洁净完好。
Check the installation of smoke and temperature sensors in public places, whether they are in good contact with the base and whether the appearance is clean and intact.
每次随机抽取不低于5%的烟感或温感,喷烟或加热后查视报警是否正确。
No less than 5% smoke or temperature sense shall be randomly selected each time. Check whether the alarm is correct after smoking or heating.
手动报警按钮,检查安装是否牢固,有无破损及丢失。

Check whether the manual alarm button is firmly installed, damaged or lost.
每次随机抽取不低于5%的手动报警按钮,进行模拟报警,测试报警功能是否正常。
At least 5% of the manual alarm buttons are randomly selected each time to simulate the alarm and test whether the alarm function is normal.
对楼层内各模块箱进行外观检查,外接线是否固定良好。
Check the appearance of each module box in the floor and whether the external wiring is well fixed.
对联动控制柜上的按钮每次按10%的比例进行功能试验,控制功能正常。
The function test of the button on the linkage control cabinet is carried out according to the proportion of 10% each time, and the control function is normal.
对火灾报警控制柜、联动控制柜等进行清扫除尘。线路松动,应进行紧固。对自检、消音、复位功能检查,主电源与备用电源切换、报警检查。
Clean and dust the fire alarm control cabinet and linkage control cabinet. If the line is loose, it shall be fastened. Check the self inspection, silencing and reset functions, and check the switching between main power supply and standby power supply and alarm.