川消气体灭火系统模拟启动试验的注意事项

来源:http://www.cx-fire.com/ 日期:2022-07-19

为验证气体灭火系统的可靠性能,气体灭火系统工程建设完成后,需要进行模拟启动试验。模拟启动试验应在气体灭火系统、报警系统等安装调试完成后进行。那么在进体灭火系统模拟启动试验时应该注意什么?
In order to verify the reliable performance of the gas fire extinguishing system, a simulated start-up test is required after the completion of the gas fire extinguishing system project. The simulated start-up test shall be carried out after the installation and commissioning of gas fire extinguishing system, alarm system, etc. So what should we pay attention to when conducting the simulated start-up test of gas fire extinguishing system?
测试依据:
Test basis:
《气体灭火系统施工及验收规范》GB50263-2007
Code for construction and acceptance of gas fire extinguishing systems (gb50263-2007)
测试内容:
Test content:
1.手动开始实验
1. Start the experiment manually
2.自动启动测试
2. Automatic start test
准备:
get ready:
1、气体报警系统和气体灭火系统已安装调试完毕,具备测试工具(秒表、声级计、万用表、点位仪、点位测试仪等)。
1. The gas alarm system and gas fire extinguishing system have been installed and debugged, and have test tools (stopwatch, sound level meter, multimeter, point position meter, point position tester, etc.).
2.人员应检查所有线路是否连接良好。
2. Professionals should check whether all lines are well connected.
3、在人员的指导下,拆下启动气体灭火系统的电磁阀,进行模拟试验。
3. Under the guidance of professionals, dismantle the solenoid valve that starts the gas fire extinguishing system and conduct a simulation test.
测试方法:
Test method:
1、手动模拟开机测试可进行如下:
1. The manual simulated startup test can be carried out as follows:
(1)按下手动启动按钮,观察相关动作信号及联动设备是否正常运行(如声光报警、启动输出端负载响应、关闭通风空调等)。
(1) Press the manual start button and observe whether the relevant action signals and linkage equipment operate normally (such as audible and visual alarm, starting the load response at the output end, turning off the ventilation and air conditioning, etc.).
(2)手动启动压力信号反馈装置,观察相关保护区门外的气体排放指示灯是否正常。
(2) Manually start the pressure signal feedback device and observe whether the gas emission indicator outside the relevant protection zone is normal.
2、自动模拟开机测试可按以下方法进行:
2. The automatic simulated startup test can be carried out according to the following methods:
(1)将灭火控制器的启动输出端连接到灭火系统相应保护区的驱动装置上。驱动装置应与阀作用机构脱开。也可以用与驱动器的启动电压和电流相同的负载来代替。
(1) Connect the starting output end of the fire extinguishing controller to the driving device of the corresponding protection area of the fire extinguishing system. The driving device shall be disconnected from the valve action mechanism. It can also be replaced by a load with the same starting voltage and current as the driver.
(2)人工模拟火警在保护区内做出任何动作,观察单次火警信号输出(如警铃、蜂鸣器等)后相关报警设备是否正常动作。
(2) Manually simulate the fire alarm to make any action in the protection area, and observe whether the relevant alarm equipment operates normally after a single fire alarm signal output (such as alarm bell, buzzer, etc.).
(3)手动模拟一个火灾报警器保护区内的另一个火灾探测器,观察复合火灾报警信号(如声光报警、启动负载)输出后相关动作信号及联动设备是否正常运行在输出端,关闭通风和空调)。、防火阀等)。
(3) Manually simulate a fire alarm to activate another fire detector in the protection area, and observe whether the relevant action signals and linkage equipment operate normally at the output end after the output of the composite fire alarm signal (such as audible and visual alarm, starting load), and turn off ventilation and air conditioning) Fire damper, etc.).
川消
测试结果的判断:
Judgment of test results:
川消小编认为模拟启动试验结果应符合下列要求:
Chuanxiao Xiaobian believes that the simulation start-up test results should meet the following requirements:
1、延迟时间与设定时间一致,响应时间符合要求;
1. The delay time is consistent with the set time, and the response time meets the requirements;
2、声光报警信号正确;
2. Sound and light alarm signals are correct;
3、联动设备动作正确;
3. The action of linkage equipment is correct;
4、驱动装置可靠。
4. The driving device is reliable.
6、测试注意事项:
6. Test precautions:
1、本试验需要严格按照人员的指导进行,以免损坏设备或伤害人员。
1. This test needs to be carried out in strict accordance with the guidance of professionals to avoid damage to equipment or injury to personnel.
2、试验前应将电磁阀从瓶组上拆下,以免误操作启动气体灭火系统。
2. Before the test, the solenoid valve should be removed from the bottle group to avoid misoperation and start the gas fire extinguishing system.
3、试验结束后,应将气体灭火系统复位检查。
3. After the test, reset the gas fire extinguishing system for inspection.
气体灭火系统的模拟试验是每个项目完成后都需要进行的试验。主要目的是保证气体灭火系统的可靠性。需要人员进行测试。用户还可以了解更多,以确保安装的气体灭火系统。设备可以正常使用。更多相关内容就来关注网站http://www.cx-fire.com信息吧!
The simulation test of gas fire extinguishing system is required after the completion of each project. The main purpose is to ensure the reliability of the gas fire extinguishing system. Professional personnel are required for testing. Users can also learn more to ensure the installation of gas fire extinguishing system. The equipment can be used normally. Follow the website for more relevant content http://www.cx-fire.com Information!
上一篇:灭火器的压力表区域相关事项了解
下一篇:七氟丙烷灭火系统按是否有管网分类讲述