室外消火栓有着严格的设置要求内容
来源:http://www.cx-fire.com/ 日期:2022-07-21
室外消火栓供水系统由消防水源、消防给水设备、室外消防给水管网和室外消火栓灭火设施组成。那么它都有这样的设置要求吗?
The outdoor fire hydrant water supply system consists of fire water source, fire water supply equipment, outdoor fire water supply pipe network and outdoor fire hydrant fire extinguishing facilities. Does it have such setting requirements?
川消户外消火栓设置范围
Setting range of Chuanxiao outdoor fire hydrant
1、在城市、住宅区、工厂、仓库等的规划和建筑设计中,必须同时设计消防给水系统;城镇(包括住宅区、商业区、开发区、工业区等)应在消防车可以通过的街道沿线。建立市政消火栓系统。
1. In the planning and architectural design of cities, residential areas, factories, warehouses, etc., fire water supply systems must be designed at the same time; Towns (including residential areas, commercial areas, development areas, industrial areas, etc.) should be along the streets where fire engines can pass. Establish a municipal fire hydrant system.
2、民用建筑、厂房(仓库)、储罐(区)、堆场周围应设置室外消火栓。
2. Outdoor fire hydrants shall be set around civil buildings, plants (warehouses), storage tanks (areas) and storage yards.
3、用于消防救援和消防车停放的屋顶,应安装室外消火栓系统。
3. Outdoor fire hydrant system shall be installed on the roof used for fire rescue and fire truck parking.
4、耐火等级不低于Ⅱ级,建筑体积小于等于3000m”的E类厂房:或人口不超过500人的住宅区,建筑面积不超过两层楼不得设置室外消防给水系统。
4. Class E plants with fire resistance rating not less than class II and building volume not less than 3000m "; or residential areas with a population of not more than 500 and a building area not more than two floors shall not be equipped with outdoor fire water supply system.

Chuanxiao outdoor fire hydrant
1、建筑物内室外消火栓的布置,除应符合本节的规定外,还应符合市政消火栓一章的有关规定。
1. In addition to the provisions of this section, the layout of outdoor fire hydrants in buildings shall also comply with the relevant provisions of the chapter on municipal fire hydrants.
2、建筑物内室外消火栓的数量应根据室外消火栓的设计流量和保护半径计算确定。保护半径不应大于150m。每个室外消火栓的出水量应按10~15L/s计算,室外消火栓应均匀分布在建筑物周围。建筑物消防面一侧的室外消火栓数量不应少于2个。
2. The number of outdoor fire hydrants in the building shall be determined according to the design flow and protection radius of outdoor fire hydrants. The protection radius shall not be greater than 150m. The water output of each outdoor fire hydrant shall be calculated as 10~15l/s, and the outdoor fire hydrant shall be evenly distributed around the building. The number of outdoor fire hydrants on one side of the fire-fighting surface of the building shall not be less than 2.
3、人防工程、地下工程等建筑物的出入口附近应设置室外消火栓,出入口距离不小于5m。不应大于40m;小于7m,距离加油站或油库不小于15m。
3. Outdoor fire hydrants shall be set near the entrances and exits of civil air defense works, underground works and other buildings, and the distance between the entrances and exits shall not be less than 5m. Not more than 40m; Less than 7m, and not less than 15m away from the gas station or oil depot.
4、A、B、C级储液罐区、液化烃罐区等构筑物的室外消火栓,宜设在防火堤或防护墙外。消防栓不应计算在内。
4. Outdoor fire hydrants of structures such as grade A, B and C liquid storage tank areas and liquefied hydrocarbon tank areas should be set outside the fire dike or protective wall. Fire hydrants shall not be counted.
5、工艺单元区域内使用高压或临时高压消防供水系统的场所,应在其周围设置室外消火栓。数量应按设计流量计算确定,间距不大于60.0m。当工艺安装区宽度大于120m时,室外消火栓应安装在安装区的路边。
5. Outdoor fire hydrants shall be set around the places where high-pressure or temporary high-pressure fire water supply system is used in the process unit area. The quantity shall be calculated and determined according to the design flow, and the spacing shall not be greater than 60.0m. When the width of the process installation area is greater than 120m, the outdoor fire hydrant should be installed on the roadside of the installation area.
6、室外消防进水管装有防倒流器,发生火灾时室外消火栓因水头损失不能满足规范要求时,应安装室外消火栓在回流防止器前面。
6. The outdoor fire water inlet pipe is equipped with a backflow preventer. In case of a fire, the outdoor fire hydrant should be installed in front of the backflow preventer if it cannot meet the specification requirements due to the head loss.
Outdoor fire hydrants have strict setting requirements. That's it. After all, using this equipment is related to safety, so do you need to pay more attention to relevant matters? Pay attention to us http://www.cx-fire.com Learn more.