川消室内消火栓箱内应配置这几样东西

来源:http://www.cx-fire.com/ 日期:2022-07-21

室内消火栓是用于扑灭建筑物初期火灾的消防设施,也是我们常见的消防设施之一。那么室内消火栓箱内一般应配置什么呢?实际上消火栓箱是放置消火栓及其附件的场所,一般放置以下设施、设备和器材。
Indoor fire hydrant is a fire-fighting facility used to extinguish the initial fire of buildings, and it is also one of our common fire-fighting facilities. So what should be configured in the indoor fire hydrant box? In fact, the fire hydrant box is the place where the fire hydrant and its accessories are placed. Generally, the following facilities, equipment and apparatus are placed.
1、消防给水管道与消火栓接口
1. Interface between fire water supply pipeline and fire hydrant
室内消防给水管道铺设在消火栓箱内,并与消火栓箱内的消火栓接口连接。消火栓接口中心要求离地1.1米,要求消火栓接口垂直于墙面或平行于墙面。插口不得影响消火栓箱门的操作和关闭,插口直径为65mm;
The indoor fire water supply pipeline is laid in the fire hydrant box and connected with the fire hydrant interface in the fire hydrant box. The center of the fire hydrant interface is required to be 1.1m above the ground, and the fire hydrant interface is required to be perpendicular to or parallel to the wall. The socket shall not affect the operation and closing of the fire hydrant box door, and the socket diameter is 65mm;
川消
2.消防水带和消防枪
2. Fire hose and fire gun
消火栓箱一般配有消防水带和消防水枪。要求软管不得与箱底接触放置,以免水软管吸收空气中的水分而腐烂。同时,软管的长度不应大于25米。;需要配置的水枪喷嘴直径不小于19mm;
Fire hydrant boxes are generally equipped with fire hoses and fire water guns. It is required that the hose shall not be placed in contact with the bottom of the box, so as to prevent the water hose from absorbing moisture in the air and rotting. At the same time, the length of the hose should not be greater than 25 meters.; The diameter of the water gun nozzle to be configured shall not be less than 19mm;
3.消防水带卷盘
3. Fire hose reel
在一些建筑物中,由于规范要求,必须安装消防水带卷盘,而消防水带卷盘一般安装在消火栓箱内。川消小编提醒您,不得小于19mm,螺栓开口直径应为25mm,软管卷盘管口直径不得小于6mm;
In some buildings, due to the requirements of the specification, the fire hose reel must be installed, and the fire hose reel is generally installed in the fire hydrant box. Chuanxiao Xiaobian reminds you that it should not be less than 19mm, the diameter of bolt opening should be 25mm, and the diameter of hose reel nozzle should not be less than 6mm;
4.灭火器
4. Fire extinguisher
有的消火栓箱分为上下两部分。消防栓及其附件放在上面,灭火器放在下面。一般建筑物内的火灾种类有A类火灾、B类火灾或C类火灾,所以配置ABC干粉灭火器是适用的。1点应配置的灭火器数量由计算确定,但一个配置点配置的灭火器数量不得少于2个,不超过5个。
Some fire hydrant boxes are divided into upper and lower parts. The fire hydrant and its accessories are placed on the top, and the fire extinguisher is placed below. Generally, the fire types in buildings include class a fire, class B fire or class C fire, so it is applicable to configure ABC dry powder fire extinguishers. The number of fire extinguishers that should be configured at one point is determined by calculation, but the number of fire extinguishers configured at one configuration point should not be less than 2 and not more than 5.
以上就是关于室内消火栓箱内应配置这几样东西的全部内容,希望对大家有所帮助。对于我们生活中的消防设备,必须定期进行检查,防止出现损坏或是老化等现象。想了解更多相关内容,请继续关注我们http://www.cx-fire.com
The above is all about the configuration of these things in the indoor fire hydrant box. I hope it will help you. The fire-fighting equipment in our life must be checked regularly to prevent damage or aging. For more information, please continue to follow us http://www.cx-fire.com !