随着使用湿式报警阀的人越来越多,要注意任何产品不能光使用而不去维护,那样寿命会很快殆尽的,湿式报警阀也是如此,所以今天呢,我们了解一下川消湿式报警阀的日常维护注意事项是什么?
As more and more people use the wet alarm valve, it should be noted that any product can not be used without maintenance, so the service life of the wet alarm valve will soon be exhausted. So, today, let's learn about the daily maintenance precautions of Chuanxiao wet alarm valve?
1、检查阀瓣上橡胶垫片的密封面,附着在橡胶密封垫上的污物和异物;橡胶密封件使用寿命一般在十八个月内,若有磨损、老化,应及时更换。
1. Check the sealing surface of the rubber gasket on the valve disc and remove the dirt and foreign matters attached to the rubber gasket; The service life of rubber seal is generally within 18 months. If there is wear and aging, it should be replaced in time.
2、半年检查一次流动水压,检查时打开放水阀,警铃发出报警声响,此时,压力表所显示的压力值不应明显下降,如果下降较为显着,应检查闸阀是否堵塞或未开;如果压力表所显示的压力下降比较明显,且警铃不报警,应检查湿式报警止回阀的阀瓣启动是否正常。
2. Check the flowing water pressure once a half year. Open the drain valve and the alarm bell will sound. At this time, the pressure value displayed on the pressure gauge should not drop significantly. If the drop is significant, check whether the gate valve is blocked or not opened; If the pressure drop shown on the pressure gauge is obvious and the alarm bell does not alarm, check whether the valve disc of the wet alarm check valve is started normally.
3、应半月检查一次警铃转动是否正常,检查时打开放水阀,报警阀瓣因水压差而自动打开,水流入延迟器经20-30秒后,警铃发出报警声响。
3. Check whether the alarm bell rotates normally once every half a month. Open the drain valve during the inspection. The alarm valve flap will open automatically due to the water pressure difference. After 20-30 seconds, the alarm bell will sound.
如果警铃不发出响声,应检查整个警铃管道,排除其水垢、泥沙及污物,使水流畅通,防止报警失灵。若警铃校验旋塞关闭后,警铃仍发声,则应检查校验旋塞是否关紧、在报警阀的环形水槽上是否积聚了障碍物、报警阀瓣下的橡胶是否老化或皱褶。使用iFire消防宝处理日常为保,准确掌握设备信息,对这些故障应及时排除。
If the alarm bell does not sound, check the entire alarm bell pipe to remove its scale, sediment and dirt, so as to make the water flow smooth and prevent alarm failure. If the alarm bell still sounds after the alarm bell check cock is closed, check whether the check cock is closed tightly, whether obstacles are accumulated on the annular water tank of the alarm valve, and whether the rubber under the alarm valve flap is aging or wrinkled. Use ifare fire protection treasure to handle daily affairs, accurately grasp equipment information, and timely eliminate these faults.
川消
4、每年应检查一次密封件和阀座密封圈环形槽内的小孔和密封面,污物或异物;密封面不应划伤,小孔保持通畅,不能修复应予更换。
4. Check the small holes and sealing surfaces in the annular groove of the sealing element and valve seat sealing ring once a year to remove dirt or foreign matters; The sealing surface shall not be scratched, and the small hole shall be kept unobstructed. If it cannot be repaired, it shall be replaced.
5、根据消防用水的水质情况,定期打开过滤器上排污口,清理脏物,保持管路通畅。
5. According to the water quality of fire water, regularly open the drain outlet on the filter, clean the dirt and keep the pipeline unblocked.
6、检查和清理延迟器内的脏物,节流小孔不应有异物堵塞。
6. Check and clean the dirt in the retarder, and the throttle orifice shall not be blocked by foreign matters.
7、日常注意消防水池的水位及水压和相应阀门所处状态是否符合规范要求。
7. Daily attention shall be paid to whether the water level and pressure of the fire pool and the state of the corresponding valves meet the specification requirements.
看完小编对湿式报警阀的日常维护注意事项的介绍,是不是已经知道要怎么去维护它了呢?看完介绍是不是就觉得很简单了呢,那还在等什么,赶紧行动吧。更多注意事项就来我们网站http://www.cx-fire.com咨询吧!
After reading Xiaobian's introduction to the daily maintenance precautions of the wet alarm valve, do you know how to maintain it? After reading the introduction, do you think it is very simple? What are you waiting for? Hurry up. For more information, please visit our website http://www.cx-fire.com Consult!