川消_萃联
气体灭火系统
自动喷水灭火系统
当前位置:首页 > 新闻中心川消大空间灭火装置电源装置调试应符合要求

川消大空间灭火装置电源装置调试应符合要求

来源:http://www.cx-fire.com/ 日期:2022-09-05

是大空间灭火装置能在发生火灾时自动探测着火部位,并主动喷水。这种系统需要在建筑内部装修和系统施工完成后进行系统调试,下面是川消大空间灭火装置电源装置调试内容。
It is a large space fire extinguishing device that can automatically detect the fire position and actively spray water in case of fire. This system needs to be debugged after the interior decoration and system construction of the building are completed. The following is the debugging of the power supply device of the fire extinguishing device in Chuanxiao large space.
1)电源装置的容量应符合设计和现行有关标准的要求;
1) The capacity of the power supply device shall meet the requirements of the design and current relevant national standards;
2)电源装置的交流输入和直流备用输入(蓄电池组)应能自动切换;
2) The AC input and DC standby input (battery pack) of the power supply device shall be able to switch automatically;
3)电源装置的交流输入和直流备用输入切换时,不应影响大空间智能灭火装置的工作状态;
3) When the AC input and DC standby input of the power supply device are switched, the working state of the large space intelligent fire extinguishing device shall not be affected;
4)电源装置的直流备用输入(蓄电池组)充放电功能正常。
4) The DC standby input (battery pack) of the power supply device has normal charging and discharging functions.
川消
大空间智能灭火装置调试应符合下列要求:
Commissioning of large space intelligent fire extinguishing device shall meet the following requirements:
1)大空间智能灭火装置的调试应逐个进行;
1) Commissioning of large space intelligent fire extinguishing devices shall be carried out one by one;
2)通电后复位状态、监视状态正常;
2) Reset status and monitoring status are normal after power on;
3)使系统处于手动状态,在大空间智能灭火装置进入监视状态后,在其保护范围内,模拟火灾发生,待火源稳定燃烧后,在规定的时间内,大空间智能灭火装置应发出报警、启动水泵、打开电磁阀等信号。
3) Make the system in manual state. After the large space intelligent fire extinguishing device enters the monitoring state, simulate a fire within its protection range. After the fire source is stably burning, the large space intelligent fire extinguishing device should send out signals such as alarm, start the water pump, open the solenoid valve, etc. within the specified time.
此时使系统变为自动状态,则水泵应立即启动、电磁阀应立即打开、喷头应立即喷水灭火。火源熄灭后,可人工复位大空间智能灭火装置,使其重新处于监视状态;
At this time, if the system becomes automatic, the water pump should be started immediately, the solenoid valve should be opened immediately, and the sprinkler should be sprayed immediately. After the fire source is extinguished, the large space intelligent fire extinguishing device can be reset manually to put it back in the monitoring state;
4)大空间智能灭火装置的大流量喷头在喷水过程中转动均匀、灵活。
4) The large flow nozzle of the large space intelligent fire extinguishing device rotates evenly and flexibly during the spraying process.