川消_萃联
气体灭火系统
自动喷水灭火系统
当前位置:首页 > 新闻中心分区控制阀常见的五方面故障处理

分区控制阀常见的五方面故障处理

来源:http://www.cx-fire.com/ 日期:2022-09-06

分区控制阀分为开式、闭式、预作用式几种控制方式,当然在使用期间也难免会有问题存在,为了做好预防措施,我们需要知道常见的故障问题有什么,下面川消小编为您解答。
Partition control valves are divided into open, closed and pre acting control modes. Of course, there will be problems during use. In order to take preventive measures, we need to know what the common fault problems are. Below, Chuanxiao Xiaobian will answer them for you.
1.分区控制阀不方便操作、误操作
1. The partition control valve is inconvenient and misoperated
(1)故障原因分析:为了防止误操作,把控制阀设置在防护区外较高处不便于操作;设置位置合适时,其他人员误动作。
(1) Fault cause analysis: in order to prevent misoperation, it is not convenient to set the control valve at a high place outside the protection area; When the setting position is appropriate, other personnel will make mistakes.
(2)故障处理:控制阀外设一个有机玻璃箱,并注明“非消防勿动”。
(2) Troubleshooting: a plexiglass box is set outside the control valve, and "do not move unless for fire protection" is marked.
2.瓶组系统分区控制阀手动启动装置无法动作
2. The manual starting device of the partition control valve of the bottle group system cannot operate
(1)故障原因分析:瓶组系统采用电磁启动阀作为分区控制阀时,电磁启动阀设有手动紧急启动装置,紧急情况时,将手动保险销拔出,拍击手动按钮,即可使启动阀动作,启动装置喷雾灭火。电磁启动阀检测合格后,动作机构的弹簧已处于压紧待发状态,为防止在安装、调试及运输过程中产生误动作,动作机构多由辅助保险销锁定,在系统投入使用后容易忘记拔出保险销,导致电磁启动阀动作机构无法动作。
(1) Failure cause analysis: when the bottle group system uses the electromagnetic starting valve as the divisional control valve, the electromagnetic starting valve is equipped with a manual emergency starting device. In case of emergency, pull out the manual safety pin and tap the manual button to actuate the starting valve and start the device to spray fire. After the electromagnetic start-up valve passes the test, the spring of the action mechanism is in a compressed and ready to start state. In order to prevent misoperation during installation, commissioning and transportation, the action mechanism is mostly locked by the auxiliary safety pin. It is easy to forget to pull out the safety pin after the system is put into use, resulting in the failure of the action mechanism of the electromagnetic start-up valve.
(2)故障处理:待系统安装调试完毕投入使用时,须将辅助保险销拔出,并将此项工作明确写入使用单位的系统运行管理操作、维护规程中。
(2) Fault handling: when the system is put into use after installation and commissioning, the auxiliary safety pin must be pulled out, and this work must be clearly written into the system operation management operation and maintenance procedures of the user.
川消
3.电动阀不动作
3. Electric valve does not operate
(1)故障原因分析:电源接线接触不良;超出电源电压允许范围;阀芯内混入杂质卡死;电动装置烧毁或短路。
(1) Fault cause analysis: poor power connection; Exceeding the allowable range of power supply voltage; Impurities mixed in the valve core are stuck; The electric device is burnt or short circuited.
(2)故障处理:压紧电源接线;调整电压允许范围内;清洗阀芯;更换电动装置。
(2) Fault handling: press the power supply wiring; Adjust the voltage within the allowable range; Clean the valve core; Replace the electric device.
4.高压球阀渗漏
4. Leakage of high-pressure ball valve
(1)故障原因分析:管道内水有杂质割伤密封垫;手柄紧定六角螺丝松动;O型圈损坏。
(1) Fault cause analysis: impurities in the water in the pipeline cut the sealing gasket; The set hexagon screw of the handle is loose; The O-ring is damaged.
(2)故障处理:更换密封垫并清洗管道;旋紧紧定六角螺丝;更换O型圈。
(2) Fault handling: replace the sealing gasket and clean the pipeline; Tighten the set hexagon screw; Replace the O-ring.
5.压力开关报警
5. Pressure switch alarm
(1)故障原因分析:高压球阀渗漏;高压球阀未关闭到位;压力开关未复位;压力开关损坏。
(1) Fault cause analysis: leakage of high-pressure ball valve; High pressure ball valve is not closed in place; The pressure switch is not reset; The pressure switch is damaged.
(2)故障处理:见上文高压球阀渗漏故障处理方法;用手柄将电动阀关闭零位;按下压力开关进行复位;更换压力开关。
(2) Fault treatment: see the above treatment method for leakage of high-pressure ball valve; Close the electric valve to the zero position with the handle; Press the pressure switch to reset; Replace the pressure switch.
分区控制阀常见的五方面故障处理如上述所讲,您对此有什么想咨询的呢?欢迎关注我们网站http://www.cx-fire.com,咨询更多事项!
As mentioned above, the five common faults of partition control valves are handled. What do you want to consult about them? Welcome to our website http://www.cx-fire.com Yes, for more information!
上一篇:川消消防泵泵组常见故障分析与处理
下一篇:川消大空间灭火装置电源装置调试应符合要求