川消消防泵泵组常见故障分析与处理

来源:http://www.cx-fire.com/ 日期:2022-09-06

消防泵体几乎处处都很重要,无论是间接到场工作的火线还是后台正在安装中起到支持感化,为了让大家更为顺利的使用它,下面川消小编就来消防泵泵组常见故障分析与处理。
The fire pump body is very important almost everywhere, whether it is the fire line that is indirectly working on the scene or the background that is being installed. In order to make everyone use it more smoothly, the following Sichuan Xiaobian will analyze and deal with common faults of the fire pump unit.
1.泵组连接处有渗漏
1. There is leakage at the connection of pump unit
(1)故障原因分析:连接件松动;连接处O型圈或密封垫损坏;连接件损坏。
(1) Fault cause analysis: loose connector; The O-ring or sealing gasket at the connection is damaged; The connector is damaged.
(2)故障处理:拧紧连接件;更换O型圈或密封垫;更换连接件。
(2) Fault handling: tighten the connector; Replace O-ring or sealing gasket; Replace the connector.
2.泵组出口压力低
2. Low outlet pressure of pump unit
(1)故障原因分析:泵组测试阀未关闭;泵组进线电源反相;高压泵损坏;使用流量超出额定值。
(1) Fault cause analysis: the test valve of the pump unit is not closed; The incoming power supply of the pump unit is in reverse phase; High pressure pump is damaged; The used flow exceeds the rated value.
(2)故障处理:关闭泵组测试阀;调整进线电源相序;更换高压泵;在泵组额定值内工作。
(2) Fault handling: close the test valve of the pump unit; Adjust the phase sequence of incoming power supply; Replace the high-pressure pump; Operate within the rated value of the pump unit.
川消
3.泵组不启动
3. The pump unit does not start
(1)故障原因分析:高压泵接触器未闭合;泵组停止触点断开;LOGO!未执行程序;电源未接通;断水水位保护。
(1) Fault cause analysis: high pressure pump contactor is not closed; The stop contact of the pump unit is disconnected; LOGO! The procedure is not executed; The power supply is not connected; Water cut-off level protection.
(2)故障处理:闭合接触器;闭合泵组停止触点;检修LOGO!必要时更换;接通电源;恢复调节水箱水位。
(2) Fault handling: close the contactor; Close the stop contact of the pump unit; Maintenance LOGO! Replace if necessary; Power on; Restore the water level of the regulating water tank.
4.稳压泵频繁启动
4. The stabilized pressure pump starts frequently
(1)故障原因分析:管道有渗漏;泄压阀密封不好;测试阀未关紧;单向阀密封垫上粘连杂质。
(1) Fault cause analysis: the pipeline has leakage; Poor sealing of safety relief valve; The test valve is not closed tightly; Impurities are adhered on the sealing gasket of one-way valve.
(2)故障处理:管道渗漏点补漏;检修泄压阀;完全关闭测试阀;清洗单向阀并清洁水箱及管道。
(2) Fault treatment: repair the leakage point of the pipeline; Overhaul the safety relief valve; Completely close the test valve; Clean the check valve and water tank and pipeline.
5.稳压泵规定时间内不能恢复压力
5. The stabilized pressure pump cannot recover the pressure within the specified time
(1)故障原因分析:管道内残存空气;管道有渗漏;高压球阀渗漏;稳压泵出口压力低;稳压泵损坏。
(1) Fault cause analysis: residual air in the pipeline; The pipeline has leakage; Leakage of high-pressure ball valve; The outlet pressure of the stabilized pressure pump is low; The stabilized pressure pump is damaged.
(2)故障处理:完全排除管道空气;管道渗漏点补漏;见下文高压球阀渗漏故障处理方法;调节稳压泵压力调节螺丝;更换稳压泵。
(2) Troubleshooting: completely eliminate the air in the pipeline; Repair the leakage point of the pipeline; See the following treatment methods for leakage of high-pressure ball valve; Adjust the pressure adjusting screw of the stabilized pressure pump; Replace the stabilized pressure pump.
川消消防泵泵组常见故障分析与处理就讲解到这里了,您如果还有什么问题没有得到解答,可以随时来我们网站http://www.cx-fire.com咨询!
This is all about the analysis and treatment of common faults of Chuanxiao fire pump unit. If you have any questions that haven't been answered, you can come to our website at any time http://www.cx-fire.com consulting service