泡沫消火栓一般都安装在漏天场所,常年爱日晒雨淋,外表涂漆日久易遭剥蚀、脱落、导致外表生锈,因此要定期检修,以延长使用寿命。下面来讲讲川消泡沫消火栓的七点安装要求。
Foam fire hydrants are generally installed in places with leaks. They are always exposed to the sun and rain. The surface is easy to be peeled, peeled off and rust after being painted for a long time. Therefore, regular maintenance is required to extend the service life. Next, we will talk about the seven point installation requirements of Chuanxiao foam fire hydrant.
1)一般情况下,室外管道选用地上式泡沫消火栓或地下式泡沫消火栓,室内管道选用室内泡沫消火栓或消火栓箱。
1) Generally, the outdoor pipeline shall use the ground foam fire hydrant or underground foam fire hydrant, and the indoor pipeline shall use the indoor foam fire hydrant or fire hydrant box.
2)地上式泡沫消火栓要垂直安装,地下式泡沫消火栓要安装在消火栓井内的泡沫混合液管道上。
2) The above ground foam fire hydrant shall be installed vertically, and the underground foam fire hydrant shall be installed on the foam mixture pipeline in the fire hydrant well.
3)地上式泡沫消火栓的大口径出液口要朝向消防车道,以便于消防车或其他移动式的消防设备吸液口的安装。地上式泡沫消火栓上的大口径出液口,在一般情况下不用,而是利用其小口径出液口即KWS65型接口,接上消防水带和泡沫枪进行灭火,当需要利用消防车或其他移动式消防设备灭火,而且需要从泡沫混合液管道上设置的消火栓上取用泡沫混合液时,才使用大口径出液口。
3) The large diameter liquid outlet of the ground foam fire hydrant shall face the fire lane, so as to facilitate the installation of the liquid suction port of the fire truck or other mobile fire-fighting equipment. The large diameter liquid outlet on the ground foam fire hydrant is not used under normal circumstances, but its small diameter liquid outlet, namely KWS65 type interface, is used to connect the fire hose and foam gun to extinguish the fire. The large diameter liquid outlet is only used when the fire truck or other mobile fire-fighting equipment is required to extinguish the fire, and the foam mixture is required to be taken from the fire hydrant set on the foam mixture pipeline.
川消
4)地下式泡沫消火栓要有明显长久性标志,一般在井盖上都有标志,但由于锈蚀或被灰尘覆盖,甚违反规定堆放物资,使得在使用时很难快速找到消火栓,为了可在明显处设置标志,如在附近的墙上设置标志。
4) Underground foam fire hydrants should have obvious permanent signs, usually on the well cover, but it is difficult to quickly find the fire hydrant in use because of rust or dust cover, or even stacking materials in violation of regulations. For safety, signs can be set at obvious places, such as on the adjacent wall.
5)地下式泡沫消火栓顶部与井盖底面的距离不得大于0.4m,且不小于井盖半径,这样做是为了消防人员操作快捷方便,以免下井操作,也避免井盖被乳坏而损坏消火栓。
5) The distance between the top of the underground foam fire hydrant and the bottom of the well cover shall not be more than 0.4m, and shall not be less than the radius of the well cover. This is for the convenience of the fire fighters, so as to avoid the operation in the well and the damage of the well cover to the fire hydrant.
6)室内泡沫消火栓的栓口方向宜向下或与设置泡沫消火栓的墙面成90°,栓口离地面或操作基面的局度一般为1.1m,允许偏差为±20mm,坐标的允许偏差为20mm。
6) The nozzle of indoor foam fire hydrant should be downward or 90 ° to the wall where the foam fire hydrant is installed. The location of the nozzle from the ground or the operating base surface is generally 1.1 m, with the allowable deviation of ± 20 mm and the allowable deviation of coordinates of 20 mm.
7)泡沫泵站内或站外附近泡沫混合液管道上设置的泡沫消火栓,要符合设计要求。
7) The foam fire hydrant set on the foam mixture pipeline inside or near the foam pump station shall meet the design requirements.
川消泡沫消栓的主要部件选用了高耐腐蚀材料、同时主要部件处于油箱内,始终能得到充分的润滑。长时间不用、不保养也不会锈死、卡住。您可以来我们网站http://www.cx-fire.com咨询了解一番!
The main parts of Chuanxiao foam hydrant are made of high corrosion resistant materials, and the main parts are in the oil tank, which can always be fully lubricated. If it is not used or maintained for a long time, it will not rust or get stuck. You can come to our website http://www.cx-fire.com Ask and understand!
上一篇:泡沫喷头工作原理及安装要点