消防水炮验收的一般规定
General provisions for acceptance of fire water monitor
供水管道应与生产、生活用水管道分开。
Water supply pipes shall be separated from production and domestic water pipes.
供水管道不宜与泡沫混合液的供给管道合用。寒冷地区的湿式供水管道应采取防冻保护措施,干式管道应设排除管道内积水和空气的设施。管道设计应满足设计流量、压力和开启喷射的时间等要求。
The water supply pipeline should not be used together with the supply pipeline of foam mixture. Anti freezing protection measures shall be taken for wet water supply pipes in cold areas, and facilities for removing water and air from the pipes shall be set for dry pipes. The pipe design shall meet the requirements of design flow, pressure and time from opening to spraying.
消防水源的容量不应小于规定灭火时间和冷却时间内需要同时使用水炮、泡沫炮、保护水幕喷头等用水量及供水管道内充水量之和。该容量可减去规定灭火时间和冷却时间内补充的水量。
The capacity of fire water source shall not be less than the sum of water consumption of water monitor, foam monitor, protective water curtain nozzle and water filling in the water supply pipeline within the specified fire extinguishing time and cooling time. This capacity can be reduced by the amount of water replenished during the specified fire extinguishing time and cooling time.
消防水泵的供水压力应能满足系统中水炮、泡沫炮喷射压力的要求。
The water supply pressure of the fire pump shall meet the requirements of the spray pressure of the water monitor and foam monitor in the system.

灭火剂及加压气体的补给时间不宜大于48h。
The supply time of fire extinguishing agent and pressurized gas shall not be longer than 48h.
水炮系统和泡沫炮系统从启动泡沫喷射水或泡沫的时间不应大于5min,干粉炮系统从启动炮口喷射干粉的时间不应大于2min。
The time from the start of the water monitor system and the foam monitor system to the foam water or foam injection shall not be more than 5min, and the time from the start of the dry powder monitor system to the muzzle dry powder injection shall not be more than 2min.
消防水炮验收的布置
Arrangement of fire water monitor acceptance
室内消防水炮的布置数量不应少于两门,其布置高度应保证消防炮的射流不受上部建筑结构件的影响,并应能使两门水炮的水射流同时到达被保护区的任一部份。室内系统应采用湿式给水系统,消防炮位处应设置消防水泵启动按钮。
The number of indoor fire water monitors shall not be less than two, and their arrangement height shall ensure that the jet of fire monitors is not affected by the superstructure structure, and the jet of two water monitors can reach any part of the protected area at the same time. The indoor system shall adopt the wet water supply system, and the fire pump start button shall be set at the fire gun position.
设置消防炮平台时,其结构强度应能满足消防炮喷射反作用力的要求,结构设计应能满足消防炮正常使用要求。
When the fire monitor platform is set, its structural strength shall meet the requirements of the reaction force of the fire monitor, and the structural design shall meet the requirements of the normal use of the fire monitor.
室外消防炮的布置应能使消防炮射流完全覆盖被保护场所及被保护物,且应满足灭火强度及冷却强度的要求。
The outdoor fire monitor shall be arranged so that the fire monitor jet can completely cover the protected place and objects, and shall meet the requirements of fire extinguishing intensity and cooling intensity.
消防炮应设置在被保护场所常年主导风向的上风向;
The fire monitor shall be set in the upwind direction of the perennial dominant wind direction of the protected place;
当灭火对象高度较高、面积较大时,或在消防炮的射流受到较高大障碍物的阻挡时,应设置消防炮塔。
When the fire extinguishing object is high and large, or when the jet of the fire monitor is blocked by high and large obstacles, the fire turret shall be set.