川消报警阀组在使用时避免十个问题存在

来源:http://www.cx-fire.com/ 日期:2022-12-26

报警阀组是自动喷水灭火系统的关键组件之一,规范对报警阀组及其组件的安装作了规定,今天我们分享川消报警阀组在使用时避免十个问题存在。
The alarm valve group is one of the key components of the automatic sprinkler system. The specification specifies the installation of the alarm valve group and its components. Today, we share ten problems to avoid when using the Sichuan Fire Alarm Valve Group.
1)雨淋报警阀或预作用报警阀的电磁阀入口处未安装过滤器,水中杂质会影响电磁阀的启闭;
1) No filter is installed at the inlet of solenoid valve of deluge alarm valve or pre action alarm valve, and impurities in water will affect the opening and closing of solenoid valve;
2)与其它报警阀并联安装的雨淋报警阀或预作用报警阀,其控制腔进水管路入口未安装止回阀,当报警阀入口水压产生波动时,可能引起其他雨淋报警阀或预作用报警阀的误动作;
2) For deluge alarm valve or pre action alarm valve installed in parallel with other alarm valves, check valve is not installed at the inlet of the water inlet pipe of the control chamber. When the water pressure at the inlet of the alarm valve fluctuates, it may cause misoperation of other deluge alarm valves or pre action alarm valves;
3)雨淋报警阀或预作用报警阀组的复位阀,在系统正常运行时设在常开状态,造成报警阀防复位功能失效,甚还会导致报警阀无法正常开启,无法供水灭火;
3) The reset valve of deluge alarm valve or pre action alarm valve group is set to the normally open state during the normal operation of the system, which causes the failure of the anti reset function of the alarm valve, and even causes the alarm valve to fail to open normally and cannot supply water for fire fighting;
4)预作用报警阀组配套的空压机组、空气维持装置安装不符合要求;
4) The installation of air compressor unit and air maintenance device matched with pre action alarm valve group did not meet the requirements;
川消
5)安装在喷淋保护现场的报警阀组,未设置防护围栏和警示标志,容易被碰撞甚损坏;
5) The alarm valve group installed at the spraying protection site is not equipped with protective fence and warning signs, which is easy to be collided or even damaged;
6)报警阀组安装高度太低或太高,操作不方便;报警阀安装部位室内地面未设置排水设施;
6) The installation height of alarm valve group is too low or too high, which makes operation inconvenient; There is no drainage facility on the indoor ground where the alarm valve is installed;
8)报警阀进出口的控制阀采用普通涡轮蝶阀,且未设置锁定阀位的锁具;
8) The control valves at the inlet and outlet of the alarm valve are ordinary turbine butterfly valves, and there is no lock to lock the valve position;
9)自动喷水灭火系统设置2个及以上报警阀组,未采用环状供水管道;
9) The sprinkler system is equipped with two or more alarm valve groups, and no circular water supply pipeline is used;
10)环状供水管道上设置的控制阀采用普通涡轮蝶阀,且未设置锁定阀位的锁具。
10) The control valve set on the annular water supply pipe adopts the ordinary turbine butterfly valve, and there is no lock to lock the valve position.
川消报警阀组在使用时避免十个问题存在相关内容就讲解完毕了,您有什么疑惑或者需求就来网站http://www.cx-fire.com留言咨询吧!