气体灭火系统投入使用要记得每月进行检查
来源:http://www.cx-fire.com/ 日期:2022-12-31
气体灭火系统投入使用时,要记得每月进行定期检查,每月检查应符合下列要求,下面
川消小编为您解答。
When the gas fire extinguishing system is put into use, remember to conduct regular inspection every month. The monthly inspection should meet the following requirements. The following section of Chuanxiao will answer for you.
应按检查类别规定对气体灭火系统进行检查,并按本规范表F做好检查记录。检查中发现的问题应及时处理。
The gas fire extinguishing system shall be inspected according to the inspection category, and inspection records shall be made according to Table F of this specification. Problems found in the inspection shall be handled in a timely manner.
每日应对低压二氧化碳储存装置的运行情况、储存装置间的设备状态进行检查并记录。
The operation of the low pressure carbon dioxide storage device and the equipment status between the storage devices shall be checked and recorded daily.
每月检查应符合下列要求:
The monthly inspection shall meet the following requirements:
1 低压二氧化碳灭火系统储存装置的液位计检查,灭火剂损失10%时应及时补充。
1. Check the liquid level gauge of the storage device of the low pressure carbon dioxide fire extinguishing system, and replenish it in time when the extinguishing agent loses 10%.
2 高压二氧化碳灭火系统、七氟丙烷管网灭火系统及IG541灭火系统等系统的检查内容及要求应符合下列规定:
2 The inspection contents and requirements of high-pressure carbon dioxide fire extinguishing system, heptafluoropropane pipe network fire extinguishing system, IG541 fire extinguishing system and other systems shall meet the following requirements:

1) 灭火剂储存容器及容器阀、单向阀、连接管、集流管、泄放装置、选择阀、阀驱动装置、喷嘴、信号反馈装置、检漏装置、减压装置等全部系统组件应无碰撞变形及其他机械性损伤,表面应无锈蚀,保护涂层应完好,铭牌和标志牌应清晰,手动操作装置的防护罩、铅封和标志应完整。
1) Fire extinguishing agent storage containers and all system components such as container valves, one-way valves, connecting pipes, collecting pipes, safety relief devices, selector valves, valve driving devices, nozzles, signal feedback devices, leak detection devices, pressure relief devices, etc. shall be free of collision deformation and other mechanical damage, the surface shall be free of rust, the protective coating shall be intact, the nameplates and signboards shall be clear, and the protective covers, lead seals and safety signs of manual operating devices shall be complete.
2) 灭火剂和驱动气体储存容器内的压力,不得小于设计储存压力的90%。
2) The pressure in the fire extinguishing agent and driving gas storage container shall not be less than 90% of the design storage pressure.
3 预制灭火系统的设备状态和运行状况应正常。
3 The equipment status and operation status of prefabricated fire extinguishing system shall be normal.
The gas fire extinguishing system shall be regularly inspected and maintained by a full-time person who has received special training and passed the examination. Come to our website if you have any questions http://www.cx-fire.com Consult!