每季度应对气体灭火系统进行1次综合检查,并应符合下列规定,接下来川消小编为您解答。
The gas fire extinguishing system should be comprehensively inspected once a quarter, and should comply with the following regulations. Next, Sichuan Xiaobian will answer for you.
1 可燃物的种类、分布情况,防护区的开口情况,应符合设计规定。
1. The type and distribution of combustibles and the opening of the protection area shall meet the design requirements.
2 储存装置间的设备、灭火剂输送管道和支、吊架的固定,应无松动。
2 The equipment, fire extinguishing agent delivery pipeline, supports and hangers between storage devices shall be fixed without looseness.
3 连接管应无变形、裂纹及老化。必要时,送法定质量检验机构进行检测或更换。
3 The connecting pipe shall be free from deformation, crack and aging. If necessary, it shall be sent to the statutory quality inspection agency for inspection or replacement.
4 各喷嘴孔口应无堵塞。
4 Nozzle orifices shall be free from blockage.
5 对高压二氧化碳储存容器逐个进行称重检查,灭火剂净重不得小于设计储存量的90%。
5 Weigh and check the high-pressure carbon dioxide storage containers one by one, and the net weight of extinguishing agent shall not be less than 90% of the designed storage capacity.
川消
6 灭火剂输送管道有损伤与堵塞现象时,应按本规范第E.1节的规定进行严密性试验和吹扫。
6 If the fire extinguishing agent delivery pipeline is damaged or blocked, the tightness test and purging shall be carried out according to the provisions of Section E.1 of this specification.
每年应按本规范第E.2节的规定,对每个防护区进行1次模拟启动试验,并应按本规范第7.4.2条规定进行1次模拟喷气试验。
Each protection area shall be subject to one simulated start test every year according to the provisions of Section E.2 of this specification, and one simulated air injection test shall be conducted according to the provisions of Article 7.4.2 of this specification.
低压二氧化碳灭火剂储存容器的维护管理应按《压力容器技术监察规程》执行;钢瓶的维护管理应按《气瓶监察规程》执行。灭火剂输送管道耐压试验周期应按《压力管道管理与监察规定》执行。
The maintenance and management of storage containers for low pressure carbon dioxide extinguishant shall be carried out in accordance with the Supervision Regulation on Safety Technology for Pressure Vessels; The maintenance and management of steel cylinders shall be carried out in accordance with the Gas Cylinder Safety Supervision Regulation. The pressure test cycle of the fire extinguishing agent transmission pipeline shall be in accordance with the Regulations on Safety Management and Supervision of Pressure Pipeline.
所以以上针对每季度应对气体灭火系统进行1次综合检查的问题进行的解答,对您有所帮助吗?更多信息了解就来我们网站http://www.cx-fire.com咨询吧!
So is the above answer to the question of conducting a comprehensive inspection of the gas fire extinguishing system once a quarter helpful to you? Come to our website for more information http://www.cx-fire.com Consult!