控制器操作与故障处理说明
Description of controller operation and troubleshooting
1.开机:打主电和备电开关。
1. Start up: turn on the main power and standby power switches.
2.开子锁:按一下键盘操作键,再按一下调分键,键盘锁灯亮允许操作。
2. Open the sub lock: press the keyboard operation key once, and then press the scoring down key, and the keyboard lock light is on to allow operation.
3.火警:主控制器显示任一回路火警,马上派人员到现场察看:
3. Fire alarm: the main controller displays any loop fire alarm, and immediately send personnel to the site to check:
①确认是火警:马上手动启动系统按防护区门口的紧急启动按钮。
① Confirm it is a fire alarm: start the system manually immediately and press the emergency start button at the entrance of the protection area.

②如果被确认为误报:按防护区门口的紧急停止键,再把误报警排除主控制器复位紧急停止按钮复位。
② If it is confirmed as a false alarm: press the emergency stop button at the door of the protection area, and then eliminate the false alarm. Reset the emergency stop button of the main controller.
4.故障:主控制器显示故障信号,看主机面板显示的是什么故障:
4. Fault: the main controller displays the fault signal, and see what fault is displayed on the host panel:
①主电:看是否停电。
① Main power: check whether there is power failure.
②备电:看备用电池连接线是否松开。
② Standby power: check whether the backup battery cable is loosened.
③回路故障:到防护区看探测器有没有松落。
③ Circuit fault: go to the protection area to see if the detector is loose.
④掉载故障:电磁阀连线有没有松开。
④ Load loss fault: whether the solenoid valve wiring is loose.
5.手动操作:如发现防护区发生火警,探测器还没有发生动作时,就需要现场人员手动启动系统。
5. Manual operation: If a fire alarm is found in the protection area and the detector has not yet acted, the on-site personnel shall manually start the system.
①直接按防护区门口的紧急启动按钮。
① Directly press the emergency start button at the door of the protection area.
②主控制器面板上也有紧急启动按钮,直接按下就可以。
② There is also an emergency start button on the main controller panel, which can be directly pressed.
The above is the instructions for the operation and troubleshooting of the heptafluoropropane fire extinguishing system controller. If you want to know more about the heptafluoropropane fire extinguishing system, please follow our website http://www.cx-fire.com Consult!