当前位置:首页 > 新闻中心川消雨淋报警阀组常见故障及原因分析

川消雨淋报警阀组常见故障及原因分析

来源:http://www.cx-fire.com/ 日期:2023-03-16

1.自动滴水阀漏水
1. The automatic drip valve leaks
故障原因分析:
Fault cause analysis:
1)产品存在质量问题。
1) The product has quality problems.
2)安装调试或者平时定期试验、实施灭火后,没有将系统侧管内的余水排尽。
2) The residual water in the side pipe of the system is not discharged completely after installation and commissioning or regular test at ordinary times and fire extinguishing.
3)雨淋报警阀隔膜球面中线密封处因施工的杂物、不干净消防用水中的杂质等导致球状密封面不能完全密封。
3) The spherical sealing surface of the deluge alarm valve diaphragm can not be completely sealed due to the sundries left by the construction and impurities in the dirty fire water.
故障处理:
Troubleshooting:
1)更换存在问题的产品或者部件。
1) Replace the defective products or parts.
2)开启放水控制阀,排除系统侧管道内的余水。
2) Open the drain control valve to drain the residual water in the pipeline at the system side.
3)启动川消雨淋报警阀,采用洁净水流冲洗在密封面处的杂质。
3) Start the deluge alarm valve of Chuanxiao, and wash the impurities left on the sealing surface with clean water.
2.复位装置不能复位
2. The reset device cannot be reset
故障原因分析:水质过脏,有细小杂质进入复位装置密封面。
Fault cause analysis: the water quality is too dirty, and there are small impurities entering the sealing surface of the reset device.
故障处理:拆下复位装置,用清水冲洗干净后重新安装,调试到位。
Troubleshooting: remove the reset device, wash it with clean water, reinstall it, and debug it in place.
川消
3.长期无故报警
3. Long-term alarm without reason
故障原因分析:
Fault cause analysis:
1)未按照安装图样进行安装调试。
1) The installation and commissioning were not carried out according to the installation drawing.
2)误将试验管路控制阀打开。
2) The test pipeline control valve was opened by mistake.
故障处理:
Troubleshooting:
1)检查各组件安装情况,按照安装图样重新进行安装调试。
1) Check the installation of each component, and carry out installation and commissioning again according to the installation drawing.
2)关闭试验管路控制阀。
2) Close the test line control valve.
4.系统测试不报警
4. No alarm during system test
故障原因分析:
Fault cause analysis:
1)消防用水中的杂质堵塞了报警管道上过滤器的滤网。
1) The impurities in the fire water blocked the filter screen of the filter on the alarm pipe.
2)水力警铃进水口处喷嘴被堵塞、未配置铃锤或者铃锤卡死。
2) The nozzle at the water inlet of the hydraulic alarm bell is blocked, the bell hammer is not equipped or the bell hammer is stuck.
故障处理:
Troubleshooting:
1)拆下过滤器,用清水将滤网冲洗干净后,重新安装到位。
1) Remove the filter, wash it with clean water, and then reinstall it in place.
2)检查水力警铃的配件,配齐组件;有杂物卡阻、堵塞的部件进行冲洗后重新装配到位。
2) Check the accessories of the hydraulic alarm bell and complete the components; The parts blocked and blocked by sundries shall be flushed and reassembled in place.
雨淋报警阀组常见故障及原因分析就讲解到这里了,感谢您的认真阅读,如果有什么想了解的其他事项或者需求,可以随时来咨询我们http://www.cx-fire.com
The common faults and cause analysis of the deluge alarm valve group will be explained here. Thank you for your careful reading. If you have any other matters or needs, please feel free to consult us http://www.cx-fire.com !