(1)当为手动灭火系统时,应以手动控制的方式进行一次喷水试验;当为自动灭火系统时,应以手动和自动控制的方式各进行一次喷水试验,系统流量、泡沫产生装置的工作压力、比例混合装置的工作压力、系统的响应时间均应达到设计要求。
(1) When using a manual fire extinguishing system, a water spray test should be conducted in a manually controlled manner; In case of an automatic fire extinguishing system, a water spray test shall be carried out manually and automatically. The system flow, the working pressure of the foam generating device, the working pressure of the proportioning device, and the response time of the system shall all meet the design requirements.
检查数量:当为手动灭火系统时,选择远的防护区或储罐;当为自动灭火系统时,选择所需泡沫混合液流量大和远的两个防护区或储罐分别以手动和自动的方式进行试验。
Inspection quantity: When using a manual fire extinguishing system, select a remote protective area or storage tank; In case of automatic fire extinguishing system, two protection areas or storage tanks with large and far foam mixture flow shall be selected for test in manual and automatic ways respectively.
(2)川消小编提醒,低倍数泡沫灭火系统按本条第1款的规定喷水试验完毕,将水放空后进行喷泡沫试验;当为自动灭火系统时,应以自动控制的方式进行;喷射泡沫的时间不宜小于1min;实测泡沫混合液的流量、发泡倍数及到达远防护区或储罐的时间应符合设计要求,混合比不应低于所选泡沫液的混合比。
(2) Sichuan Xiaobian reminds that the low expansion foam fire extinguishing system has completed the water spraying test according to the provisions of paragraph 1 of this article, and the foam spraying test is conducted after the water is emptied; When it is an automatic fire extinguishing system, it should be carried out in an automatic control manner; The time of spraying foam should not be less than 1min; The measured flow, foaming ratio and time to reach the far protection area or storage tank of foam mixture shall meet the design requirements, and the mixing ratio shall not be lower than that of the selected foam mixture.
川消
检查数量:选择远的防护区或储罐,进行一次试验。
Inspection quantity: Select a remote protective area or storage tank for one test.
(3)中倍数、高倍数泡沫灭火系统按本条第1款的规定喷水试验完毕,将水放空后进行喷泡沫试验,当为自动灭火系统时,应以自动控制的方式对防护区进行喷泡沫试验,喷射泡沫的时间不宜小于30S,实测泡沫供给速率及自接到火灾模拟信号开始喷泡沫的时间应符合设计要求,混合比不应低于所选泡沫液的混合比。
(3) The medium and high expansion foam fire extinguishing systems shall be sprayed with foam after the completion of water spraying test according to the provisions of paragraph 1 of this article. In case of automatic fire extinguishing systems, foam spraying test shall be carried out in the protection area in an automatic control manner. The time of foam spraying shall not be less than 30s. The measured foam supply rate and the time from receiving the fire simulation signal to starting to spray foam shall meet the design requirements, The mixing ratio shall not be lower than that of the selected foam concentrate.
检查数量:全数检查。
Inspection quantity: All inspections.
泡沫灭火系统的调试应符合以上所讲内容规定,希望对您有所帮助,更多事项就来我们网站http://www.cx-fire.com留言咨询吧!
The commissioning of the foam fire extinguishing system should comply with the above provisions. I hope it will be helpful to you. For more information, please come to our website http://www.cx-fire.com Leave a message for consultation!