1、消防水泵安装前应校核产品合格证,以及其规格、型号和性能与设计要求应一致,并应根据安装使用说明书安装;
1. Before installing the fire water pump, the product certificate should be verified, and its specifications, models, and performance should be consistent with the design requirements. It should be installed according to the installation and operation manual;
2、川消消防水泵安装前应复核水泵基础混凝土强度、隔振装置、坐标、标高、尺寸和螺栓孔位置;
2. Before installing the Sichuan Fire Water Pump, the foundation concrete strength, vibration isolation device, coordinates, elevation, size, and bolt hole position of the pump should be reviewed;
3、消防水泵的安装应符合现行标准《机械设备安装工程施工及验收通用规范》GB50231和《风机、压缩机、泵安装工程施工及验收规范》GB50275的有关规定;
3. The installation of fire water pumps should comply with the relevant provisions of the current national standards "General Code for Construction and Acceptance of Mechanical Equipment Installation Engineering" GB50231 and "Code for Construction and Acceptance of Fan, Compressor, and Pump Installation Engineering" GB50275;
4、消防水泵安装前应复核消防水泵之间,以及消防水泵与墙或其他设备之间的间距,并应满足安装、运行和维护管理的要求;
4. Before installing the fire water pump, the spacing between the fire water pumps, as well as between the fire water pump and the wall or other equipment, should be reviewed and meet the requirements of installation, operation, and maintenance management;
川消
5、消防水泵吸水管上的控制阀应在消防水泵固定于基础上后再进行安装,其直径不应小于消防水泵吸水口直径,且不应采用没有可靠锁定装置的控制阀,控制阀应采用沟漕式或法兰式阀门;
5. The control valve on the suction pipe of the fire water pump should be installed after the fire water pump is fixed on the foundation. Its diameter should not be less than the diameter of the fire water pump suction port, and control valves without reliable locking devices should not be used. Control valves should be ditch or flange type valves;
6、当消防水泵和消防水池位于独立的两个基础上且相互为刚性连接时,吸水管上应加设柔性连接管;
6. When the fire pump and fire pool are located on two independent foundations and are rigidly connected to each other, a flexible connecting pipe should be added to the suction pipe;
7、吸水管水平管段上不应有气囊和漏气现象。变径连接时,应采用偏心异径管件并应采用管顶平接;
7. There should be no air pockets or leaks on the horizontal section of the suction pipe. When connecting with variable diameter, eccentric reducing pipe fittings should be used and the top of the pipe should be flat connected;
8、消防水泵出水管上应安装消声止回阀、控制阀和压力表;系统的总出水管上还应安装压力表和压力开关;安装压力表时应加设缓冲装置。压力表和缓冲装置之间应安装旋塞;压力表量程在没有设计要求时,应为系统工作压力的2倍~2.5倍;
8. Silencing check valves, control valves, and pressure gauges should be installed on the outlet pipe of the fire pump; A pressure gauge and pressure switch should also be installed on the main outlet pipe of the system; When installing a pressure gauge, a buffer device should be added. A cock should be installed between the pressure gauge and the buffer device; When there is no design requirement, the range of the pressure gauge should be 2 to 2.5 times the working pressure of the system;
9、消防水泵的隔振装置、进出水管柔性接头的安装应符合设计要求,并应有产品说明和安装使用说明。
9. The installation of the vibration isolation device and flexible joints of the inlet and outlet pipes of the fire water pump should meet the design requirements, and there should be product instructions and installation instructions.