川消_萃联
气体灭火系统
自动喷水灭火系统
当前位置:首页 > 新闻中心火灾报警控制器主要功能介绍

火灾报警控制器主要功能介绍

来源:http://www.cx-fire.com/ 日期:2024-01-29

作为火灾自动报警系统的控制中心,火灾报警控制器具有火灾报警功能、火灾报警控制功能、故障报警功能、屏蔽功能、监管功能、自检功能、信息显示与查询功能及电源功能等。

As the control center of the automatic fire alarm system, the fire alarm controller has functions such as fire alarm, fire alarm control, fault alarm, shielding, supervision, self inspection, information display and query, and power supply.

(1)控制器能直接或间接地接收来自火灾探测器及其他火灾报警触发器件的火灾报警信号,发出火灾报警声、光信号,指示火灾发生部位,记录火灾报警时间,并予以保持,直到手动复位。控制器具有专用火警总指示灯,控制器处于火灾报警状态时,火警示灯点亮。火灾报警信号能手动消防,当再次有火灾报警信号输入时,能再次启动。

(1) The controller can directly or indirectly receive fire alarm signals from fire detectors and other fire alarm triggering devices, emit fire alarm sound and light signals, indicate the location of the fire, record the fire alarm time, and maintain it until manually reset. The controller has a dedicated fire alarm main indicator light, which lights up when the controller is in a fire alarm state. The fire alarm signal can be manually used for firefighting, and it can be restarted when there is another fire alarm signal input.

20220611113641497.jpg

(2)控制器可设置控制输出,用于火灾报警传输设备和消防联动设备等设备的控制,每一控制输出有对应的手动直接控制按钮。

(2) The controller can set control outputs for the control of fire alarm transmission equipment and fire linkage equipment, and each control output has a corresponding manual direct control button.

(3)故障报警功能:控制器设专用故障报警总指示灯,无论控制器处于何种状态,只要有故障信号存在,该故障总指示灯点亮。当控制器内部、控制器与其连接的部件间发生故障时,控制器能在100S内发出与火灾报警信号有明显区别的故障声、光信号,故障声信号能手动,如再有故障信号输入时,能再次启动,故障光信号能保持故障排除。

(3) Fault alarm function: The controller is equipped with a dedicated fault alarm main indicator light. Regardless of the state of the controller, as long as there is a fault signal, the fault main indicator light will light up. When there is a fault inside the controller or between the controller and its connected components, the controller can emit a fault sound and light signal that is significantly different from the fire alarm signal within 100 seconds. The fault sound signal can be manually eliminated. If there is another fault signal input, it can be restarted and the fault light signal can be maintained until the fault is eliminated.

(4)控制器设专用屏蔽总指示灯,无论控制器处于何种状态,只要有屏蔽存在,该屏蔽总指示信号灯点亮。

(4) The controller is equipped with a dedicated shielding main indicator light. Regardless of the state of the controller, as long as there is shielding present, the shielding main indicator light will light up.

(5)监管功能(动作):控制器设专用监管报警状态总指示灯,无论控制器处于何种,只要有监管信号输入,该监管报警状态总指示灯点亮。

(5) Regulatory function (action): The controller is equipped with a dedicated regulatory alarm status indicator light. Regardless of the controller's status, as long as there is a regulatory signal input, the regulatory alarm status indicator light will light up.

当有监管信息输入时,控制器能在100S内发出与火灾报警信号有明显区别的监管报警声、光信号;声信号仅能手动,汉有冷的的监管信号输入时能再次启动;光信号能保持手支复位。如果监管信号仍存在,复位后监管报警状态能保持或在20S内重新建立。控制器能显示所有监管信号,当天能同时显示时可手动查询。

When there is regulatory information input, the controller can emit regulatory alarm sound and light signals that are significantly different from fire alarm signals within 100 seconds; The sound signal can only be manually eliminated, and Han Youleng's supervision signal can be restarted when input; The optical signal can be maintained until the hand is reset. If the regulatory signal still exists, the regulatory alarm status can be maintained or re established within 20 seconds after resetting. The controller can display all regulatory signals and can manually query them when they can be displayed simultaneously on the same day.

(6)自检功能:控制器能检查本机的火灾报警功能称为自检。控制器在执行自检功能期间,受其控制的外接设备和输出接点均不动作。控制器自检超过1分种或其不能自动停止时,控制器的自检功能不影响非自检部位、探测区和控制器本身的火灾报警功能。

(6) Self check function: The controller's ability to check the fire alarm function of the machine is called self check. During the self check function of the controller, the external devices and output contacts controlled by it do not operate. When the self-test of the controller exceeds 1 minute or it cannot automatically stop, the self-test function of the controller does not affect the fire alarm function of non self-test parts, detection areas, and the controller itself.

(7)信息显示与查询功能:控制器信息显示按火灾报警、监管报警及其它状态顺序由高低排列信息显示等级,高等级的状态信息优先显示,低等级状态信息显示不应影响高等级信息显示,显示的信息与对应的状态一致且易于辨识。当控制器处于某一高等级状态显示时,能通过手动操作查询其它低等级状态信息,和状态信息不交替显示。

(7) Information display and query function: The controller displays information in descending order of fire alarm, regulatory alarm, and other status. High level status information is displayed first, while low level status information should not affect the display of high level information. The displayed information should be consistent with the corresponding status and easy to identify. When the controller is in a certain high-level status display, it can manually query other low-level status information without alternating with the status information.

(8)电源功能:主机控制器具有主电源和备用电源转换装置,当主电源断电时,能自动转换到备用电源;主电源恢复时,能自动转换到主电源。控制器有主、备电源工作状态指示,主备电源转换不不使控制器产生误动作。

(8) Power function: The host controller has a main power and backup power conversion device, which can automatically switch to the backup power when the main power is cut off; When the main power supply is restored, it can automatically switch to the main power supply. The controller has the indication of the working status of the main and backup power supplies, and the conversion of the main and backup power supplies does not cause the controller to malfunction.

本文由川消友情奉献.更多有关的知识请点击:http://www.cx-fire.com我们将用真诚的态度.为您提供为的服务.更多有关的知识我们将会陆续向大家奉献.敬请期待.

This article is dedicated by Chuanxiao Youqing. For more related knowledge, please click: http://www.cx-fire.com We will provide you with comprehensive service with a sincere attitude. We will gradually contribute more relevant knowledge to everyone. Stay tuned

上一篇:建筑工程常见的消防器材设施设备有哪些?
下一篇:火灾自动报警系统介绍