高压二氧化碳气体灭火系统主要由二氧化碳储瓶、容器阀、液流单向阀、高压软管、集流管、阀、选择阀、压力讯号器、称重检漏装置、启动瓶、电磁阀、气路单向阀、喷嘴以及高压管道、管接件、瓶组架等设备、零部件和材料组成。下面川消小编来讲讲它得动作程序是怎样的吧。
High-pressure carbon dioxide gas fire extinguishing system is mainly composed of carbon dioxide storage cylinder, container valve, liquid flow check valve, high-pressure hose, collecting pipe, safety valve, selector valve, pressure signal, weighing and leak detection device, starting cylinder, solenoid valve, gas path check valve, nozzle, high-pressure pipeline, pipe fittings, bottle rack and other equipment, parts and materials. Let's talk about its action program What is it.
1、当灭火系统的开启方式置于"自动"状态:
1. When the opening mode of the fire extinguishing system is in the "automatic" state:
报警控制器在接收到同一区域内相邻两只不同类型的火灾探测器同时发出的火险信号后,会自动启动灭火控制器,系统进入喷放前30秒阶段。在期间,控制器通过设在保护区域内外的声光报警器发出紧急撤离疏散警报,并联动关闭可能影响灭火效果的有关设备(如通风机、空调、防火卷帘等)。结束,灭火控制器即向相关的电磁阀发出启动信号,打开启动瓶上的电磁阀,释放出来的高压启动气体打开相应的选择阀和二氧化碳储瓶容器阀,储瓶内的二氧化碳灭火剂经管网和喷嘴喷放到火灾区域或保护对象上,实施灭火。
After receiving the fire danger signals sent by two adjacent fire detectors of different types in the same area at the same time, the alarm controller will automatically start the fire extinguishing controller, and the system will enter the countdown phase of 30 seconds before spraying. During the countdown, the controller sends out the emergency evacuation alarm through the audible and visual alarm set inside and outside the protection area, and closes the related equipment (such as ventilator, air conditioner, fire shutter, etc.) that may affect the fire extinguishing effect. At the end of the countdown, the fire extinguishing controller will send a start signal to the relevant solenoid valve, open the solenoid valve on the starting cylinder, open the corresponding selector valve and the carbon dioxide cylinder container valve of the released high-pressure starting gas, and the carbon dioxide extinguishing agent in the cylinder will be sprayed onto the fire area or protected object through the pipe network and nozzle to put out the fire.
川消
2、当灭火系统的开启方式置于"手动"状态:
2. When the opening mode of the fire extinguishing system is in the "manual" state:
火灾探测器的动作只会引起火灾报警,不能使二氧化碳自动喷放。需要由区域内外的工作人员用手按动紧急启动按钮,才能启动二氧化碳灭火系统进行灭火。
The action of the fire detector will only cause the fire alarm, and can not cause the automatic emission of carbon dioxide. It is necessary for staff inside and outside the area to press the emergency start button manually to start the carbon dioxide fire extinguishing system to put out the fire.
3、在自动和手动失灵的情况下:
3. In case of automatic and manual failure:
操作人员还可以采用机械应急启动方式进行启动灭火。
The operator can also use the mechanical emergency start mode to start the fire fighting.
此外系统根据使用要求,可组成单元独立灭火系统、组合分配灭火系统,同时可适用于全淹没保护灭火和局部保护灭火。该系列产品具有功能完善、工作准确可靠、操作维修方便等特点。可广泛适用于易燃液体储存区、机械设备易于失火的重要部位、计算机及电子设备间、图书馆、档案馆、珍品库、变配电室、飞机汽车库、厨房及排烟管道等防护区。您有需求就来咨询我们http://www.cx-fire.com吧!
In addition, the system can form a unit independent fire extinguishing system and a combined distribution fire extinguishing system according to the use requirements, and it can also be used for total flooding protection fire extinguishing and local protection fire extinguishing. This series of products has the characteristics of complete functions, accurate and reliable work, convenient operation and maintenance, etc. It can be widely used in flammable liquid storage area, important parts of mechanical equipment prone to fire, computer and electronic equipment room, library, archives, treasure store, power transformation and distribution room, aircraft garage, kitchen, smoke exhaust pipe and other protection areas. If you have any need, please consult us http://www.cx-fire.com Come on!